beautypg.com

Eq5 ac drive operations manual, A parameters, U parameters – HP Anab EQ5 User Manual

Page 51

background image


EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Parameters A01 – A18 ~ U01 – U89 45


A Parameters

Para.

No.

NAME

LCD Display

Setting range

Unit

Min.

Unit

Factory setting

Change

During

Oper.

User

Set

value

Remark

30HP/CT
40HP/VT

40HP/CT
50HP/VT

A01 Maximum frequency 2

A01

MAX Hz-2

50 to 120Hz

Hz

1

60

N

A02 Base frequency 2

A02

BASE Hz-2

25 to 120Hz

Hz

1

60

N

A03 Rated voltage 2

(at Base frequency 2 )

A03

RATED V-2

0:

V

1

220: (230V class)

N



80 to 240V: (230V class)

380: (460V class)

320 to 480V: (460V class)

A04 Maximum voltage 2

(at Base frequency 2)

A04

MAX V-2

80 to 240V: (230V class)

V

1

220:(230V class)

N



320 to 480V: (460V class)

380:(460V class)

A05 Torque boost2

A05

TRQ BOOST2

0.0, 0.1 to 20.0

-

-

0.1

Y

A06 Electronic thermal overload relay for motor 2

A06

ELCTRN OL2

0, 1, 2

- -

1 Y

A07 (Level)

A07

OL LEVEL2

INV rated current 20%to135%

A

0.01

Motor rated current

Y

A08

(Thermal time constant)

A08

TIME CNST2

0.5 to 75.0 min

min

0.1

5.0

10.0

Y

A09 Torque vector control 2

A09

TRQVECTOR2

0, 1

- -

0

N

A10 Number of motor-2 poles

A10

M2 POLES

2 to 14 poles

poles

2

4

N

A11

Motor 2

(Capacity)

A11

M2-CAP

Up to 30HP:0.01 to 60HP

HP

0.01

Motor capacity

N

40HP and above:0.01to800HP

A12

(Rated current)

A12

M2-Ir

0.00 to 2000A

A

0.01

Motor rated current

N

A13

(Tuning)

A13

M2 TUN1

0, 1, 2

- -

0

N

A14

(On-line Tuning)

A14

M2 TUN2

0, 1

- -

0

N

A15

(No-load current)

A15

M2-Io

0.00 to 2000A

A

0.01

TWMC standard rated value

N

A16

(%R1 setting)

A16

M2-%R1

0.00 to 50.00%

%

0.01

TWMC standard rated value

Y

A17

(%X setting)

A17

M2-%X

0.00 to 50.00%

%

0.01

TWMC standard rated value

Y

A18

(Slip compensation control 2)

A18

SLIP COMP2

0.00 to 15.00Hz

Hz

0.01

0.00

Y


U Parameters

U01 Maximum

compensation

frequency

U01

USER 01

0 to 65535

- 1

75 A

during braking torque limit

U02 1st S-shape level at acceleration

U02

USER 02

1 to 50%

%

1

10

NA

U03 2nd S-shape level at acceleration

U03

USER 03

1 to 50%

%

1

10

NA

U04 1st S-shape level at deceleration

U04

USER 04

1 to 50%

%

1

10

NA

U05 2nd S-shape level at deceleration

U05

USER 05

1 to 50%

%

1

10

NA

U08

Main DC link

capacitor

(Initial value)

U08

USER 08

0 to 65535

-

1 xxxx A

U09

(Measured value)

U09

USER 09

0 to 65535

-

1 0 A

U10 PC board capacitor powered on time

U10

USER 10

0 to 65535h

h

1

0

A

U11 Cooling fan operating time

U11

USER 11

0 to 65535h

h

1

0

A

U13 Magnetize current vibration damping gain

U13

USER 13

0 to 32767

-

1 819

410 A

U15 Slip compensation filter time constant

U15

USER 15

0 to 32767

-

1 556

546 A

U23 Integral gain of continuous operation

U23

USER 23

0 to 65535

-

1

1738 1000 A

at

power

failure

U24 Proportional gain of continuous

U24

USER 24

0 to 65535

-

1

1024 1000 A

operation at power failure

U48 Input phase loss protection

U48

USER 48

0, 1, 2

-

-

-75HP 100HP- NA

0 1

U49 RS-485 protocol selection

U49

USER 49

0, 1

-

-

1 NA

U59

Braking-resistor function select(up to 30HP/CT,

40HP/VT)

U59

USER 59

00 to A8(HEX)

-

1

00 NA

Manufacturer's function(40HP/CT, 50HP/VT or

more)

U60 Regeneration avoidance at deceleration

U60

USER 60

0, 1

-

-

0 NA

U61 Voltage detect offset and gain adjustment

U61

USER 61

--30HP/CT, 40HP/VT:0 (Fixed.)

-

-

0 A

40HP/CT,

50HP/CT--:0, 1, 2

U89 Motor overload memory

U89

USER 89

0.1

-

-

1 A

retention