TECO

–Westinghouse Motor Company Function Explanation 54

Holding time



Time

Forward rotation

Starting frequency

Stopping frequency

Output frequency


The starting frequency can be set to reserve the torque at
startup and can be sustained until the magnetic flux of the
motor is being established.
Frequency: This function sets the frequency at startup.

Setting range: 0.1 to 60Hz


Holding time: This function sets the holding time

during which the start frequency is sustained at startup.



Set values: 0.1 to 10.0 seconds

The holding time does not apply at the time of switching

between forward and reverse.

The holding time is not included in the acceleration time.

The holding time also applies when pattern operation

(C21) is selected. The holding time is included in the
timer value.

This function sets the frequency at stop.

Setting range: 0.0 to 60.0Hz











The operation does not start when the starting frequency
is less than the stopping frequency or when the setting
frequency is less than the stopping frequency.



This function adjusts the carrier frequency, correct

adjustment of which prevents resonance with the
machine system, reduces motor and inverter noise, and
also reduces leakage current from output circuit wiring.


Nominal applied motor

Setting range

EQ5

30HP/CT or less
40HP/VT or less

0.75 to 15kHz

40HP/CT to 100HP/CT
50HP/VT to 125HP/VT

0.75 to 10kHz

125HP/CT or more
150HP/VT or more

0.75 to 6kHz



Carrier frequency

Low High

Motor noise

High Low

Output current waveform

Bad Good

Leakage current

Small amount Large amount

Noise occurrence

Extremely low High









The tone of motor noise can be altered when the carrier

frequency is 7kHz or lower. Use this function as
required.



Setting range: 0 , 1, 2 , 3




Monitor data (e.g.,output frequency, output current) can
be output to terminal FMA as a DC voltage. The amplitude
of the output can also be adjusted.
This function adjusts the voltage value of the monitor

item selected in F31 when the monitor amount is 100%.
A value from 0 to 200 (%) can be set in 1% steps.


Setting range: 0 to 200%











This function selects the monitor item to be output to

terminal FMA.

Set

value

Monitor item

Definition of 100% monitor amount

0

Output frequency 1
(before slip compensation)

Maximum output frequency

1

Output frequency 2
(after slip compensation)

Maximum output frequency

2

Output current

Rated output current of
inverter x 2

3

Output voltage

230V series: 250V
460V series: 500V

4

Output torque

Rated torque of motor x 2

5

Load rate

Rated load of motor x 2

6

Power consumption

Rated output of inverter x 2

7

PID feedback amount

Feedback amount of 100%

8

PG feedback amount
(only when option is installed)

Synchronous

speed

at

maximum frequency

9

DC link circuit voltage

230V series: 500V
460V series: 1,000V

10

Universal AO

0 to 10V output through
communication and not related to
inverter operation.

※The power consumption shows "0" during regenerative load.

F30:200%

Higher than 10V

F30:0%

F30:50%

5V

10V

F30:100%

100%

50%

FMA

termin

al

ou

tpu

t

vol

tag

e

F23

F24

Starting frequency (frequency)

Start frequency (Holding time)

F25

Stop frequency

F30

FMA (voltage adjust)

FMA (function)

F31

F26

Motor sound (carrier frequency)

F27

Motor sound (sound tone)

Notes:
1. Reducing the set value adversely affects the output current

waveform (i.e., higher harmonics), increases motor loss, and
raises motor temperature. For example, at 0.75 kHz, reduce
the motor torque by about15%.

2 Increasing the set value increases inverter loss and increases

the inverter temperature.

F 2 3

S T A R T

H z

F 2 4

H O L D I N G

t

F 2 5

S T O P

H z

F 2 6

M T R

S O U N D

F 2 7

M T R

T O N E

F 3 0

F M A

V - A D J

F 3 1

F M A

F U N C