HP Anab EQ5 User Manual
Page 60
TECO
–Westinghouse Motor Company Function Explanation 54
Holding time
Time
Forward rotation
Starting frequency
Stopping frequency
Output frequency
The starting frequency can be set to reserve the torque at
startup and can be sustained until the magnetic flux of the
motor is being established.
Frequency: This function sets the frequency at startup.
Setting range: 0.1 to 60Hz
Holding time: This function sets the holding time
during which the start frequency is sustained at startup.
Set values: 0.1 to 10.0 seconds
The holding time does not apply at the time of switching
between forward and reverse.
The holding time is not included in the acceleration time.
The holding time also applies when pattern operation
(C21) is selected. The holding time is included in the
timer value.
This function sets the frequency at stop.
Setting range: 0.0 to 60.0Hz
The operation does not start when the starting frequency
is less than the stopping frequency or when the setting
frequency is less than the stopping frequency.
This function adjusts the carrier frequency, correct
adjustment of which prevents resonance with the
machine system, reduces motor and inverter noise, and
also reduces leakage current from output circuit wiring.
Nominal applied motor
Setting range
EQ5
30HP/CT or less
40HP/VT or less
0.75 to 15kHz
40HP/CT to 100HP/CT
50HP/VT to 125HP/VT
0.75 to 10kHz
125HP/CT or more
150HP/VT or more
0.75 to 6kHz
Carrier frequency
Low High
Motor noise
High Low
Output current waveform
Bad Good
Leakage current
Small amount Large amount
Noise occurrence
Extremely low High
The tone of motor noise can be altered when the carrier
frequency is 7kHz or lower. Use this function as
required.
Setting range: 0 , 1, 2 , 3
Monitor data (e.g.,output frequency, output current) can
be output to terminal FMA as a DC voltage. The amplitude
of the output can also be adjusted.
This function adjusts the voltage value of the monitor
item selected in F31 when the monitor amount is 100%.
A value from 0 to 200 (%) can be set in 1% steps.
Setting range: 0 to 200%
This function selects the monitor item to be output to
terminal FMA.
Set
value
Monitor item
Definition of 100% monitor amount
0
Output frequency 1
(before slip compensation)
Maximum output frequency
1
Output frequency 2
(after slip compensation)
Maximum output frequency
2
Output current
Rated output current of
inverter x 2
3
Output voltage
230V series: 250V
460V series: 500V
4
Output torque
Rated torque of motor x 2
5
Load rate
Rated load of motor x 2
6
Power consumption
Rated output of inverter x 2
7
PID feedback amount
Feedback amount of 100%
8
PG feedback amount
(only when option is installed)
Synchronous
speed
at
maximum frequency
9
DC link circuit voltage
230V series: 500V
460V series: 1,000V
10
Universal AO
0 to 10V output through
communication and not related to
inverter operation.
※The power consumption shows "0" during regenerative load.
F30:200%
Higher than 10V
F30:0%
F30:50%
5V
10V
F30:100%
100%
50%
FMA
termin
al
ou
tpu
t
vol
tag
e
F23
F24
Starting frequency (frequency)
Start frequency (Holding time)
F25
Stop frequency
F30
FMA (voltage adjust)
FMA (function)
F31
F26
Motor sound (carrier frequency)
F27
Motor sound (sound tone)
Notes:
1. Reducing the set value adversely affects the output current
waveform (i.e., higher harmonics), increases motor loss, and
raises motor temperature. For example, at 0.75 kHz, reduce
the motor torque by about15%.
2 Increasing the set value increases inverter loss and increases
the inverter temperature.
F 2 3
S T A R T
H z
F 2 4
H O L D I N G
t
F 2 5
S T O P
H z
F 2 6
M T R
S O U N D
F 2 7
M T R
T O N E
F 3 0
F M A
V - A D J
F 3 1
F M A
F U N C