Caution – HP Anab EQ5 User Manual
Page 90
TECO
–Westinghouse Motor Company Function Explanation 84
becomes longer than the set deceleration time.
◆In case of F14 set value : 3.
The output frequency is lowered by the control by
which the DC voltage of the main circuit is kept
constant from the regeneration energy, so that the
inverter may continue operation when momentary
power failure occurs.
The response is adjusted with U23 and U24 at this
time.
◆Calculate the integral gain using the following formula.
value
set
23"
U
"
2
gain
Integral
16
[ms]
PI
calculator
H15
Set value
DC voltage of the
main circuit
Output frequency
command
|f
*
|
I gain:U23
P gain:U24
|f
*
|
0
Output frequency
command
|f
**
|
Input phase loss protection
U48
◆This function selects operation of input phase loss or
power supply unbalance protection.
U 4 8
U S E R 4 8
Setting range : 0 to 2
Set value
Operation
0
Active (without reactor (ACR/DCR))
1
Active (with reactor (ACR/DCR))
2
Inactive
When "2" is set to U48, protection
operation of the inverter to input phase
loss or power supply voltage unbalance
does not work. If you use it as it is,
there is a possibility of damaging an
inverter and
failure may result.
RS-485 protocol selection
U49
◆The protocol of RS-485 communication is changed.
U 4 9
U S E R 4 9
Set value : 0, 1
Set value
Operation
0
FGI-bus
1
Modbus-RTU
Instruction manual and specifications are prepared
about communicative details. Contact TWMC.
◆When function code F13 (electronic thermal)is set to 2,
both the type of the braking resistor and connection
circuit are set. Factory setting is set to nominal applied
resistor and the number of resistor is one. When the
power load capacities of resistor are increased, set the
factory setting properly
U 5 9
U S E R
5 9
Setting range : 0 to A8 (HEX)
Setting of ten
’s digit ( type selection )
Set
value
Resistance
[Ω]
Capacity
[W]
Duty
cycle
[%ED]
0
-
-
10%
1
100
200
2
40
400
3
33
400
4
20
800
5
15
900
6
200
200
7
160
400
8
130
400
9
80
800
A
60
900
Setting of unit
’s digit (connection circuit selection)
Se
t va
lue
Braking-resistor
*1)
Duty
cycle
[%ED]
Synthetic
resistance
[Ω]
Power
consumption per
resistance
[comparatively]
Use
number
Connection circuit
0
1
DB
P
10%
R
100%
1
2
DB
P
20%
2R
50%
2
2
DB
P
20% (1/2)R
50%
3
4
DB
P
40%
R
25%
4
3
DB
P
30%
3R
33%
5
6
DB
P
50% (3/2)R
17%
6
9
DB
P
50%
R
11%
7
4
DB
P
40%
4R
25%
8
8
DB
P
50%
2R
12.5%
1) It is limited by the %ED value of the braking transistor
inside the inverter.
CAUTION
△
!