EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Serial Communications Modbus 118

Data format [16] Operating state:

15 14

13

12 11 10 9 8 7 6 5 4 3 2 1 0

BUSY WR RL

ALM

DEC

ACC

IL

VL

TL

NUV

BRK

INT

EXT

REV

FWD

(All bit are ON or active by 1)

FWD: Forward operation

IL:

Current limiting

REV:

Reverse operation

ACC: Under acceleration

EXT: DC braking active (or pre-excitation)

DEC: Under deceleration

ALM:

Inverter

fault

INT:

No Output

RL: Transmission

valid

BRK:

Braking active

WR:

Function writing privilege

NUV: DC link voltage is established

0: Keypad panel

(undervoltage at 0)

1: RS-485

TL:

Torque limiting

2: Fieldbus (option)

VL:

Voltage limiting

BUSY: Processing data write

Data format [17] Type code:

15

14

13

12

11

10 9 8 7 6 5 4 3 2 1 0

Type Generation Series

Voltage

series

Code

Type

Generation

Series

Voltage series

1 -

EQ5

-

-

2 - - -

-

3

EQ5

-

-

230V three phase

4

-

-

-

460V three phase

5

-

-

USA

575V three phase

6 - - -

-

Data format [18] Code setting (1–4 figures):

15

14

13

12

11

10 9 8 7 6 5 4 3 2 1 0

Data 4

Data 3

Data 2

Data 1

Data format [19] Amperage value Decimal data (positive ):

Min. unit 0.01 inverter capacity is not more than 30HP/CT, 40HP/VT.
Min unit 0.01 for not less than 40HP/CT, 50HP/CT.

Example: F11 (electronics thermal overload relay 1 level) 107.0A (40HP) 107.0 X 10=1070=042E

H

F11 (electronics thermal overload relay 1 level) =3.60A (1HP) 3.60 X 100=360=0168

H