HP Anab EQ5 User Manual
Page 85
TECO
–Westinghouse Motor Company Function Explanation 79
-To suppress vibration with a frequency roughly equivalent
to the value "H24 D-gain," decrease the value of H24. If
there is residual vibration with 0.0, decrease the value of
"H22 P-gain."
R
e
sp
o
n
se
Before
adjustment
After
adjustment
Time
This filter is for feedback signal input from terminal [12]
or [C1]. This filter stabilizes operation of the PID control
system. A set value that is too large, however,
deteriorates response.
H 2 5
F B
F I L T E R
Setting range: 0.0 to 60.0 seconds
Set this function active when the motor has a PTC
thermistor for overheat protection
Set value 0: Inactive
1: Active
Connect the PTC thermistor as shown in the figure
below.
Turn on switch “PTC” on the control PCB.
T
he trip mode is activated by “OH2:External thermal
relay tripped.”
PTC
thermistor
H27
(Level)
Comparator
OH2
DC10V
Resistor
250 Ohom
0V
13
C1
11
ON OFF
PTC
1k Ohom
The voltage input to terminal [C1] is compared to the set
voltage (Level). When the input voltage is equal to or
greater than the set voltage (Level), "H26 PTC thermistor
(Mode select)," starts.
Setting range: 0.00 to 5.00V
The PTC thermistor has its own alarm temperature. The
internal resistance value of the thermistor largely change
at the alarm temperature. The operation (voltage) level
is set using this change in the resistance value.
Internal resistance of
PTC thermistor
Rp2
Rp1
Temperature
Alarm
temperature
The figure in "H26 PTC thermistor (Mode select)," shows
that resistor 250
and the thermistor (resistance value
Rp) are connected in parallel. Hence, voltage Vc
1
(Level) at terminal [C1] can be calculated by using the
following formula.
]
[
・
・
V
10
Rp
250
Rp
250
1000
Rp
250
Rp
250
Vc
1
The operation level can be set by bringing Rp in the Vc
1
calculation formula into the following range.
Rp
1
< Rp
< Rp
2
To obtain Rp easily, use the following formula.
[Ω]
2
Rp
Rp
Rp
2
1
H 2 6
P T C
M O D E
H26
PTC thermistor (Mode select)
H27
PTC thermistor (Level)
H 2 7
P T C
L E V E L
H25
PID control (Feedback filter)