EQ5 AC Drive Operations Manual
_______________________________________________________________________
TECO – Westinghouse Motor Company Serial Communications Modbus 114
Function data Registers
Address
Code
Name
Unit
Variable Range
Min.
Unit
Read/
Write
Data
Format
1800 S08
Acceleration time F07
s
0.1–3600.0
0.1 R/W
3
1801 S09
Deceleration time F08
s
0.1–3600.0
0.1 R/W
3
1802 S10
Torque limit level 1
(driving) F40
%
20.00 –200.00, 999
(EQ5:20.00-150.00)
1.00 R/W
5
1803 S11
Torque limit level 2
(braking) F41
%
0.00, 20.00–200.00, 999
(EQ5:20.00-150.00)
1.00 R/W
5
Notes: 1) The writing of data out of range is treated as out of range error.
2) Use a value of 7FFF
H
to enter 999 for torque limit functions.
Monitoring parameter registers
Address Code
Description
Unit
Range
Min.
Unit
Read/Write
Data
Format
2049 M01
Frequency command
(final command)
-
- 20000–20000
(max. frequency at ±
20000)
1 R [2]
2053 M05
Frequency command
(final command)
Hz 0.00-120.00)
0.01
R
[5]
2054 M06
Actual frequency
-
- 20000–20000
(max. frequency at ±
20000)
1 R [2]
2055
M07 Actual torque value
%
- 200.00–200.00 0.01
R [6]
2056
M08 Torque current
%
- 200.00–200.00 0.01
R [6]
2057 M09
Output
frequency
Hz
0.00-120.00)
0.01
R
[5]
2058 M10
Motor output (input
electric power)
%
0.00–200.00
0.01 R
[5]
2059 M11
Output current r. m. s.
%
0.00–200.00 (inverter
rating at 100.00)
0.01 R
[5]
2060
M12 Output voltage r. m. s.
V
0.0–600.0 1.0
R
[3]
2061 M13
Operation command
(final command)
-
Refer to data format
[14]
- R [14]
2062 M14
Operating state
-
Refer to data format
[16]
- R [16]
2063 M15
Universal output
terminal data
-
Refer to data format
[15]
- R [15]
2064
M16 Fault memory 0
-
Refer to data format
[10]
- R [10]
2065
M17 Fault memory 1
2066
M18 Fault memory 2
2067
M19 Fault memory 3
2068 M20
Integrated operating
time
h
0–65535
1 R [1]
2069
M21 DC link voltage
V
0–1000 1
R
[1]
2071 M23
Type code
-
Refer to data format
[17]
- R [17]
2072 M24
Inverter capacity code
-
Refer to data format
[11]
- R [11]
Cont.