Eq5 ac drive operations manual, Caution – HP Anab EQ5 User Manual
Page 5
EQ5 AC Drive Operations Manual
_______________________________________________________________________
TECO – Westinghouse Motor Company
Compliance with UL
Compliance with UL/cUL standards [Applicable to products with UL/cUL mark]
Caution
Tightening torque and wire range: Refer to Table 2-3-5 in Section 2
Apply the following power supply specifications to the inverter:
Inverter Model
Maximum input voltage
Input source current
EQ5 - 20P2 - N1 to EQ5 - 2032 - N1
AC240V
Not more than 100,000A
EQ5 - 2040 - C to EQ5 - 2150 - C
EQ5 - 40P5 - N1 to EQ5 - 4032 - N1
AC480V
EQ5 - 4040 - C to EQ5 - 4800 - C
Caution
* [CAUTION] Hazard of electrical shock. Disconnect incoming power before working on this control.
* [CAUTION] Dangerous voltage exists until charge light is off.
* [WARNING]
* More than one live parts inside the inverter.
* Type1 “INDOOR USE ONLY”
The inverter is approved as a part used inside a panel. Install it inside a panel.
* Suitable for use on a circuit capable of delivering not more than 100,000rms symmetrical amperes.
* Use 60/75C copper wire only.
* A Class2 circuit wired with class1 wire.
* Field wiring connections must be made by a UL Listed and CSA Certified closed-loop terminal connector
sized for the wire gauge involved. Connector must be fixed using the crimp tool specified by the
connector manufacturer.
* Connect the power supply to main power supply terminals via the Molded-case circuit breaker (MCCB) or
a ground fault circuit interrupter (GFCI) to conform to the UL Listing Mark.
(See Instruction Manual basic connection diagram Fig.2-3-1).
* When using auxiliary control-power input (R0, T0), connect as per Basic connection diagram Fig.2-3-1.
* Solid state motor overload protection is provided in each model.