EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company

Compliance with UL


Compliance with UL/cUL standards [Applicable to products with UL/cUL mark]

Caution

Tightening torque and wire range: Refer to Table 2-3-5 in Section 2

Apply the following power supply specifications to the inverter:

Inverter Model

Maximum input voltage

Input source current

EQ5 - 20P2 - N1 to EQ5 - 2032 - N1

AC240V

Not more than 100,000A

EQ5 - 2040 - C to EQ5 - 2150 - C

EQ5 - 40P5 - N1 to EQ5 - 4032 - N1

AC480V

EQ5 - 4040 - C to EQ5 - 4800 - C



Caution

* [CAUTION] Hazard of electrical shock. Disconnect incoming power before working on this control.

* [CAUTION] Dangerous voltage exists until charge light is off.
* [WARNING]
* More than one live parts inside the inverter.
* Type1 “INDOOR USE ONLY”

The inverter is approved as a part used inside a panel. Install it inside a panel.

* Suitable for use on a circuit capable of delivering not more than 100,000rms symmetrical amperes.
* Use 60/75C copper wire only.
* A Class2 circuit wired with class1 wire.
* Field wiring connections must be made by a UL Listed and CSA Certified closed-loop terminal connector

sized for the wire gauge involved. Connector must be fixed using the crimp tool specified by the
connector manufacturer.

* Connect the power supply to main power supply terminals via the Molded-case circuit breaker (MCCB) or

a ground fault circuit interrupter (GFCI) to conform to the UL Listing Mark.
(See Instruction Manual basic connection diagram Fig.2-3-1).

* When using auxiliary control-power input (R0, T0), connect as per Basic connection diagram Fig.2-3-1.
* Solid state motor overload protection is provided in each model.