beautypg.com

HP Anab EQ5 User Manual

Page 121

background image

EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Serial Communications Modbus 115

2073 M25 ROM

version

- 0–64999 1

R

[1]

2074 M26 Transmission error processing code

-

Refer to data format [20]

-

R [20]

2075 M27

Frequency command at alarm (final
command)

-

- 20000–20000 (max. frequency
at ±20000 )

1 R

[2]

2079 M31

Frequency command at alarm (final
command)

Hz 0.00-120.00) 0.01 R

[5]

2080 M32

Actual frequency at alarm

-

- 20000–20000
(max. frequency at ± 20000)

1 R

[2]

2081 M33 Actual torque at alarm

%

- 200.00 – 200.00

0.01 R

[6]

2082 M34 Torque current at alarm

%

- 200.00 – 200.00

0.01 R

[6]

2083 M35

Output frequency at alarm

Hz

0.00 – 120.00

0.01 R

[5]

2084 M36 Motor output at alarm (input power)

%

0.00–200.00 0.01 R

[5]

2085 M37

Output current rms. at alarm

%

0.00 – 200.00 (inverter rating at
100.00)

0.01 R

[5]

2086 M38

Output voltage effective value at
alarm

V 0.0 – 600.0

1.0 R

[3]

2087 M39 Operation command at alarm

-

Refer to data format [14]

-

R [14]

2088 M40 Operating state at alarm

-

Refer to data format [16]

-

R [16]

2089 M41

Universal output terminal data at
alarm

-

Refer to data format [15]

-

R [15]

2090 M42 Integrated operation time at alarm

h

0–65535

1 R

[1]

2091 M43 DC link voltage at alarm

V 0–1000

1 R

[1]

2092 M44 Inverter internal air temp.at alarm

°C 0–120

1 R

[1]

2093 M45 Cooling fin temp. at alarm

°C 0–120

1 R

[1]

2094 M46 Life of main circuit capacitor.

%

0.0–100.0 0.1

R

[3]

2095 M47 Life of printed circuit board capacitor.

h

0–65535

1 R

[1]

2096 M48 Life of cooling fan.

h

0–65535

1 R

[1]

8-4-7 Data Format Specification

All data in the data field of communication frame shall be represented by a 16 bit length word.

15

14

13

12

11

10 9 8 7 6 5 4 3 2 1 0

16 bits binary data

Data format [1] Unsigned Integer data (Positive): Min. unit 1

Example: F15 (Frequency limit, upper)= 60Hz 60 = 003C

H


Data format [2] Integer data (Positive, negative): Min. unit 1
Example: data = -20 -20 = FFEC

H


Data format [3] Unsigned Decimal data (Positive): Min. unit 0.1

Example: F17 (frequency gain setting signal) = 100.0% 100.0 X 10 = 1000 =
03E8

H


Data format [4] Decimal data (Positive, negative): Min. unit 0.1

Example: C31 (Analog input offset adjust, term.12) = - 5.0% - 5.0 X 10= - 50 =
FFCE

H


Data format [5] Unsigned Decimal data (Positive): Min. unit 0.01
Example: C05 (multi-step frequency 1) = 50.25Hz 50.25 X 100 = 5025 = 13A1

H

This manual is related to the following products: