2.29 STALL PREVENTION
Sn-10: Protective Characteristics
Data: — X X X
0
= Stall prevention enabled
Select 1 (Stall Prevention)
during acceleration
— X X X
1
= Stall prevention disabled
The stall prevention characteristics
during acceleration
determine whether stall prevention is
— X X
0
X = Stall prevention enabled
enabled or disabled during the various
during deceleration
operating modes, as well as selecting
— X X
1
X = Stall prevention disabled
the decel rate during stall prevention.
during deceleration
— X
0
X X = Stall prevention enabled
during operation at
set frequency
— X
1
X X = Stall prevention disabled
during operation at
set frequency
—
0
X X X = Decel time during stall
prevention set by bn-02
—
1
X X X = Decel time during stall
prevention set by bn-04
Cn-28: Stall Prevention Level During
Factory setting:
170
%
Acceleration (Constant Torque Region)
Range: 30 to 200 %
Cn-29: Stall Prevention Limit During
Factory setting:
50
%
Acceleration (Constant HP Region)
Range: 30 to 200 %
The stall prevention during acceleration extends the acceleration rate according to the
load status with respect to the level programmed into Cn-28 or Cn-29 (based on GPD 503
rated current; see Table A3-1) and protects the motor from stalling during acceleration.
Cn-30: Stall Prevention Level During Operation
Factory setting:
160
%
at Set Frequency
Range: 30 to 200 %
During operation while the speed is constant, if the GPD 503 output current exceeds the
stall prevention level set into Cn-30, the output frequency is reduced to a level to prevent
motor stalling. If the output current returns to a value lower than Cn-30, the output
frequency returns to its previous level.