2.29 STALL PREVENTION

Sn-10: Protective Characteristics

Data: — X X X

0

= Stall prevention enabled

Select 1 (Stall Prevention)

during acceleration

— X X X

1

= Stall prevention disabled

The stall prevention characteristics

during acceleration

determine whether stall prevention is

— X X

0

X = Stall prevention enabled

enabled or disabled during the various

during deceleration

operating modes, as well as selecting

— X X

1

X = Stall prevention disabled

the decel rate during stall prevention.

during deceleration

— X

0

X X = Stall prevention enabled

during operation at
set frequency

— X

1

X X = Stall prevention disabled

during operation at
set frequency

0

X X X = Decel time during stall

prevention set by bn-02

1

X X X = Decel time during stall

prevention set by bn-04

Cn-28: Stall Prevention Level During

Factory setting:

170

%

Acceleration (Constant Torque Region)

Range: 30 to 200 %

Cn-29: Stall Prevention Limit During

Factory setting:

50

%

Acceleration (Constant HP Region)

Range: 30 to 200 %

The stall prevention during acceleration extends the acceleration rate according to the
load status with respect to the level programmed into Cn-28 or Cn-29 (based on GPD 503
rated current; see Table A3-1) and protects the motor from stalling during acceleration.

Cn-30: Stall Prevention Level During Operation

Factory setting:

160

%

at Set Frequency

Range: 30 to 200 %

During operation while the speed is constant, if the GPD 503 output current exceeds the
stall prevention level set into Cn-30, the output frequency is reduced to a level to prevent
motor stalling. If the output current returns to a value lower than Cn-30, the output
frequency returns to its previous level.

2-44