beautypg.com

3 auto reference characteristics – Yaskawa GPD503 Drive User Manual

Page 35

background image

2.3 AUTO REFERENCE CHARACTERISTICS

Sn-06: Operation Mode

Digit 3 [ X X X X ] : Auto Reference

Select 3

Characteristics

Factory setting: X

0

X X (0 - 100%)

The setting of this digit determines how the frequency command varies with respect to
changes in the Auto Reference command input signal.

Auto Reference inputs:

terminals 13 & 17 — 0-10 VDC
terminals 14 & 17 — 4-20 mA

GPD 503

13 0-10V (20K

1

)

14 4-20 mA (250

1

17

C

AUTO

REFERENCE

= X 0 X X
= X 1 X X

100%

FREQ

CMD

0%

4mA

20mA

INPUT CURRENT (TERM. 14)

= X 0 X X
= X 1 X X

100%

FREQ

CMD

0%

0V

10V

INPUT VOLTAGE (TERM. 13)

2-4