Yaskawa GPD503 Drive User Manual
Page 59

2.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8) Continued
Data
01
: Remote/Local
Set digits of Sn-04 to X X 0 0 to select external inputs as the source for frequency
reference and operation commands. The use of a Remote/Local command input allows
switching between the Digital Operator control and the external terminal input signals,
without the need of re-programming Sn-04. If the status of the Remote/Local command
input is changed while the drive is running, the Remote/Local operation selection is not
completed until the next time the GPD 503 is stopped.
Closed = Controlled locally (Digital Operator)
Open = Controlled remotely (external terminal inputs, and Auto reference)
NOTE: If manual speed is selected
– by the external Auto/Manual switch (3SS [2-wire] or 2SS [3-wire] ),
– by jumper from term. 5 to 11 (2-wire control),
or
– by jumper from term. 6 to 11 (3-wire control),
the GPD 503 speed reference will be controlled by manual speed reference
regardless of the state of the Remote/Local input.
DESCRIPTION
DATA
FUNCTION
Signal Levels: 0 = state; 1 = pulse
14
to
1F
Not Used
20
to
2F
External fault 1
Second digit of setting is a hexadecimal
value; its four-place binary equivalent
30
to
3F
External fault 2
defines what type of external contact
40
to
4F
External fault 3
is used and how the GPD 503 will react
50
to
5F
External fault 4
when the signal input is active
See paragraph 2.12
60
DC injection braking command
Closed 0 = DC injection braking active
(RUN and JOG have priority)
See paragraph 2.8
61
Speed Search 1
Closed 1 = Speed Search operation from
maximum frequency
See paragraph 2.28
62
Speed Search 2
Closed 1 = Speed Search operation from
set frequency
See paragraph 2.28
63
Energy-saving operation
Closed 0 = Energy saving
See paragraph 2.11
64
to
FF
Not Used
DESCRIPTION
DATA
FUNCTION
Signal Levels: 0 = maintained; 1 = momentary
Table 2-2. Sn-15 thru Sn-18 Data Settings - Continued
2-26