A1-6 – Yaskawa GPD503 Drive User Manual
Page 130

CONSTANT
SET
FACTORY
USER
PARA.
NUMBER
DATA NAME
DIGIT
DATA
FUNCTION
SETTING
SETTING
REF.
Sn-11 Protective
XXXX
0
Braking resistor (heat sink
0000
Separate
Character-
mounted) not provided.
Option
istics
Overheat protection disabled.
Instruction
Select 2
Sheet
(Momentary
1
Braking resistor (heat sink
Power Loss
mounted) provided. Over-
Protection)
heat protection enabled.
XXXX
0
Fault contact status during
2.5B
auto restart: remains open
1
Fault contact status during
auto restart: closes
XXXX
0
Operation stops when momen-
2.16, 2.5A
tary power loss is detected
1
Operation continues during
momentary power loss
XXXX
—
Not used
– –
Sn-12 Protective
XXXX
0
External fault signal:
0100
2.12A
Character-
N.O. contact input
istics
Select 3
1
External fault signal:
(External
N.C. contact input
Fault Signal
XXXX
0
External fault signal
Input at
always detected
Terminal 3)
1
External fault signal only
detected during operation
XXXX
Condition when external fault
signal is detected:
00 = Ramp to stop (major failure)
01 = Coast to stop (major failure)
10 = Emergency stop (major
failure)
Time to stop
determined by
bn-04 set value
11 = Continue operation
(minor failure)
Table A1-3. System Constants (Sn-XX) - Continued
CONSTANT
SET
FACTORY USER
PARA.
NUMBER DATA NAME DIGIT DATA
FUNCTION
SETTING SETTING
REF.
A1-6