2.15 JOG REFERENCE

An-09: Jog Reference

Factory setting:

6.00

Hz

Range: 0.00 to 400.00 Hz

When jog operation is selected (either by the Digital Operator JOG key, or by external Jog
and Run signals), the GPD 503 output will ramp to the output level set by this constant.

When the Digital Operator is used, Jog can only be initiated from the stopped condition.
When the drive is running, the JOG key will have no effect on GPD 503 output.

When an external Jog signal is present, it will override the existing operation mode and
the GPD 503 will ramp to the level set by this constant.

EXAMPLES:

OPERATION FROM DIGITAL OPERATOR

FREQ. CMD

An-09 JOG

REF.

0

FREQ. CMD

An-09 JOG

REF.

0

Press and

Release

Hold JOG

JOG

Press

Press and

Release

Press

RUN

Hold JOG

JOG

STOP

2-19