2.23 SPEED COINCIDENCE

Cn-21: Speed Coincidence Frequency

Factory setting:

0.0

Hz

Range: 0.0 to 400.0 Hz

Cn-22: Speed Coincidence Bandwidth

Factory setting:

2.0

Hz

Range: 0.0 to 25.5 Hz

Speed coincidence is used to control an output contact at terminals 9 & 10, or one of the
open collector outputs at terminals 25 & 26 (with respect to terminal 27), when selected
by Sn-20 thru Sn-24.

Sn-20: Multi-function Output 1 – Contact

Data 02 , 03 , 04 or 05

(terminals 9 & 10)

(See paragraph 2.21,

Sn-21: Multi-function Output 2 – Open Collector

MULTI-FUNCTION

(terminals 25 & 27)

OUTPUT TERMINALS

Sn-22: Multi-function Output 3 – Open Collector

(Term. 9 & 10; 25-27) )

(terminals 26 & 27)

The output contact will close, or the open collector output will go low, when acceleration or
deceleration is completed, and output frequency is within the detection width shown in the
figure below.

EXAMPLE:

If Cn-21 =

20 Hz, Cn-22 = 15.0 Hz and Sn-20 = 03 , then the contact at

terminals 9 & 10 will be closed from 25 Hz to 35 Hz.

Freq.

Cn-21 + Cn-22

Ref.

Ref. – Cn-22

40 Hz

20 Hz

(Cn-21)

0

Contact
Closure

2-34