A1-9 – Yaskawa GPD503 Drive User Manual
Page 133

CONSTANT
SET
FACTORY
USER
PARA.
NUMBER
DATA NAME
DIGIT
DATA
FUNCTION
SETTING
SETTING
REF.
Sn-26
Digital Speed
XXXX
0000 = BCD input, 1% accuracy
0000
Separate
Reference
0001 = BCD input, 0.1% accuracy
Option
(DI-08)
0010 = BCD input, 0.01% accuracy
Instruction
Frequency
0011 = BCD input, 1Hz
Sheet
reference
0100 = BCD input, 0.1Hz
set mode
0101 = BCD input, 0.01Hz
selection
0110 = Reserve
0111 = Binary input, 255 / 100%
1000 = Binary input (set value
displayed in decimal on
Digital Operator)
Sn-27
Digital Output XXXX
0
DO-08 output signal
0010
Separate
Card (DO-08)
combination 1 (output
Option
data fixed)
Instruction
Sheet
1
DO-08 output signal
combination 2 (encoded
output)
Pulse Monitor
XXXX
Number of
000 = 1F
Separate
(PO-36F)
output
001 = 6F
Option
pulses
010 = 10F
Instruction
selection
011 = 12F
Sheet
100 = 36F
Sn-28
Analog Monitor XXXX
Select item to
00 = Output
0100
Separate
(AO-08 or
output from
frequency (max.
Option
AO-12)
channel 1
frequency /100%)
Instruction
01 = Output current
Sheet
(rated current
XXXX
Select item to
/100%)
output from
10 = Output voltage
channel 2
ref. (input
voltage /100%)
11 = DC voltage [Vpn]
(400V /100%)
[230V drives]
(800V /100%)
[460V drives]
(1000V /100%)
[575V drives]
Table A1-3. System Constants (Sn-XX) - Continued
CONSTANT
SET
FACTORY USER
PARA.
NUMBER DATA NAME DIGIT DATA
FUNCTION
SETTING SETTING
REF.
A1-9