Section 6. failure indication and details, 1 general – Yaskawa GPD503 Drive User Manual
Page 108

Section 6. FAILURE INDICATION AND DETAILS
6.1 GENERAL
A failure in the GPD 503 can fall into one of two categories.
A blinking "Alarm" indication is a warning that a GPD 503 trouble condition will soon
occur, or that a problem exists in the external circuitry. The GPD 503 will continue to
operate during an "Alarm" indication. "Alarm" indications are not entered into the fault
register.
A steady "Fault" indication is displayed when the GPD 503’s Fault relay has tripped
(GPD 503 shutdown). The motor coasts to a stop, and a fault signal output is present at
control circuit terminals 18 - 20.
INDICATION
(DISPLAY)
FAILURE INDICATION ITEM
DESCRIPTION
bb
External Base Block
Base Block command at multi-function terminal is active,
(blinking)
command
shutting off GPD 503 output (motor coasting). Temporary
condition, cleared when input command is removed.
bUS
Transmission error
Control data cannot be received normally for
longer than 2 seconds.
CALL
Communication ready
Drive is waiting for the PLC to establish communication.
CPF00
Transmission error or control
Transmission between GPD 503 and remote operator is
function hardware fault
not established within 5 seconds after the power supply is
(including internal RAM,
turned on. (Displayed on the remote operator.)
external RAM or PROM)
CPF01
Transmission error
Transmission error occurs 2 seconds or more
after transmission has first been established.
CPF02
Base block circuit failure
GPD 503 failure.
CPF03
NV-RAM (S-RAM) fault
GPD 503 failure.
CPF04
NV-RAM (BCC, Access Code)
GPD 503 failure. This fault may be caused after changing
fault
EPROM chips. Perform a Sn-03 Reset operation to
attempt to clear this fault.
CPF05
A/D converter failure in CPU
GPD 503 failure.
CPF06
Optional connection failure
Improper installation or wiring of option card.
CPF20
A/D converter failure
Defective option card.
CPF21
Transmission interface card
Defective option card. Check option card connector for
(option) self-analysis
proper installation.
function fault
CPF22
Model code fault
Defective option card. Check option card connector for
proper installation.
CPF23
Mutual-analysis function
Defective option card. Check option card connector for
fault
proper installation.
Table 6-1. Failure Indication and Details
INDICATION
(DISPLAY) FAULT
DESCRIPTION
6-1