Gpd 503 – Yaskawa GPD503 Drive User Manual
Page 25

1-9
3ø POWER SUPPLY (SEE NAMEPLATE DATA)
1CB
✱
GPD 503
L1 L2 L3
15
16
17
12
14
13
V/HZ PROFILE
+15Vdc
(20mA MAX)
MAN REF. IN
(0 TO 10Vdc)
FWD
▲
▲
▲
▲
▲
▲
●
●
●
FWD
RUN/STOP
OUTPUT
VOLTAGE
(%)
COM
SHIELD
4-20mA
(250
1
OUTPUT FREQUENCY
(HZ)
DIGITAL
OPERATOR
PRGM
DRIVE
DATA
ENTER
0 TO 10Vdc
(20K
1
SEE
NOTE 4
REMOTE
DRIVE FWD REV SEQ REF
DSPL
4-20mA
0-10V
ISOLATED
AUTO
REFERENCE
✱
SEE NOTE 6
1OL
✱
SEE
NOTE 2
EXT. FAULT
✱
EXT. FAULT RESET
1PB
✱
SEE
NOTE 3
TO
TERM. 12
JOG
1R
✱
2K
1
MAN SPEED
1RH
✱
2K / 2
.
5K
1
SEE NOTE 1
AUTO
MAN
3SS
✱
1SS
✱
SEE
NOTE 1
1
2
3
4
5
6
7
8
11
9
REV
EXT. FAULT
FAULT RESET
AUTO/MAN
MULTI-STEP FREQ
SELECT
JOG
SPEED
COAST STOP
(BASE BLOCK)
0 VOLTS
RUN CONTACT
RY1
10
FAULT
CONTACTS
RY2
RY2
18
19
20
ANALOG
OUTPUT
(0-10 Vdc)
OPEN
COLLECTOR
CIRCUIT
OPEN
COLLECTOR
CIRCUIT
21
22
25
26
27
RESET
FWD
REV
RUN
STOP
RY CONTACTS
CAPACITY:
1A AT 250Vac
1A AT 30Vdc
MULTI-FUNCTION
MONITOR OUTPUT
0 - +10V
2mA MAX.
MULTI-
FUNCTION
OPEN
COLLECTOR
OUTPUTS
CAPACITY:
50mA AT 48Vdc MAX.
AC MOTOR
✱
(T2)
(T1) (T3)
G
T1 T2 T3
200V 380V 440V
220/ 400/ 460V
230V 415V
VOLTAGE SELECTOR
(460V, 15HP (CT) AND ABOVE)
FACTORY SET FOR 460V
EARTH
GROUND
SEE NOTE 5
1OL
✱
SEE NOTE 2
L1 L2 L3
GPD 503 BASIC INTERCONNECT DIAGRAM FOR 2-WIRE CONTROL
(R) (S) (T)
(E)
(U) (V) (W)
2SS
✱
REV
RUN/STOP
■
z
TERMINALS 1-8:
IF INPUT FROM RELAY CONTACTS:
RATED 30Vdc OR MORE,
100mA OR MORE
IF OPEN COLLECTOR INPUT:
RATED 35Vdc OR MORE,
100mA OR MORE
B1 or
B0/–
B2 or
B1/+
FOR WIRING
DYNAMIC
BRAKING
OPTION
SEE NOTE 7
1
2
COOLING
FAN
POWER
(15HP (CT) AND ABOVE)
Figure 1-3. 230V or 460V Interconnections - 2-Wire Control
(with constant Sn-04 set to 0000, Sn-15 set to 03,
Sn-16 set to 04, Sn-17 set to 06, and Sn-18 set to 08 )
FOR UNITS
WITH "L" IN
MODEL NO.
( "L" ) (04/27/95)
– (N)
+3
(P3)