TROUBLESHOOTING CHART 7.3

OVERVOLTAGE (

ou

) FAULT INDICATION

IS INPUT AC SUPPLY

VOLTAGE CORRECT?

NO

NO

NO

NO

DECREASE TO
PROPER VOLTAGE
RANGE.

YES

YES

YES

YES

YES

DOES OV TRIP

OCCUR ONLY

DURING DECEL-

ERATION?

DOES OV TRIP

STILL OCCUR

DURING DECEL-

ERATION?

WITH GPD 503 IN
STOPPED CONDITION,
INCREASE DECELER-
ATION TIME BY
REPROGRAMMING
bn-02 OR bn-04.

REMOVE NOISE SOURCE:

• CONNECT SURGE
SUPPRESSOR TO RELAY
AND MAGNETIC CON-
TACTOR COILS.

• PROVIDE LINE FILTER
TO REMOVE NOISE ON
INPUT POWER LINE.

ERRONEOUS

OPERATION DUE

TO NOISE?

CONTROL SIGNALS TO
BASE DRIVE PCB ARE
FAULTY. REPLACE
CONTROL PCB.

IS BRAKING

OPTION

INSTALLED?

ADD BRAKING OPTION,
OR REPLACE GPD 503
WITH ONE OF LARGER
CAPACITY.

CHECK LOAD
INERTIA
REQUIREMENTS.

7-5