CONSTANT

SET

FACTORY

USER

PARA.

NUMBER

DATA NAME

DIGIT

DATA

FUNCTION

SETTING

SETTING

REF.

Sn-13 Protective

XXXX

Not Used

0100

– –

Character-
istics

XXXX

Condition when cooling fan failure

– –

Select 4

is detected:

(Overload /

00 = Ramp to stop (major failure)

Fan Fault

01 = Coast to stop (major failure)

Protection)

10 = Emergency stop (major

failure)

Time to stop
determined by
bn-12 set value

11 = Continue operation

(minor failure)

Sn-14 Protective

XXXX

0

Electronic thermal motor

0000

2.30

Character-

protection enabled

istics
Select 5

1

Electronic thermal motor

(Motor

protection disabled

Protection)

XXXX

0

Electronic thermal
protection for
variable torque

1

Electronic thermal
protection for
constant torque

XXXX

0

Short time rating disabled

1

Electronic thermal protection
- short time rating enabled

(Drive

XXXX

0

OL = 103% continuous,

(Protection)

z

150% for one minute

1

OL = 113% continuous,

125% for one minute

z This digit is “Not Used” in 230V, 30HP (CT) and below; 460V, 60HP (CT)

and below; 575V, 25HP (CT) and below.

Table A1-3. System Constants (Sn-XX) - Continued

CONSTANT

SET

FACTORY USER

PARA.

NUMBER DATA NAME DIGIT DATA

FUNCTION

SETTING SETTING

REF.

A1-7