CONSTANT
INCRE- SETTING
FACTORY
USER
PARA.
NUMBER
DATA NAME
MENT
RANGE
SETTING SETTING
REF.
Cn-14
Frequency Command
1 %
0 - 109
100
2.14
Upper Limit
Cn-15
Frequency Command
1 %
0 - 109
0
2.14
Lower Limit
Cn-16
Prohibit Frequency 1
0.1 Hz
0.0 - 400.0
0.0
2.7A
Cn-17
Prohibit Frequency 2
0.1 Hz
0.0 - 400.0
0.0
2.7A
Cn-18
Prohibit Frequency 3
0.1 Hz
0.0 - 400.0
0.0
2.7A
Cn-19
Prohibit Frequency Deadband
0.1 Hz
0.0 - 25.5
1.0
2.7B
Cn-20
Operator Display Mode
1
0 - 39999
0
2.9
Reference and Indication
Cn-21
Speed Coincidence Frequency
0.1 Hz
0.0 - 400.0
0.0
2.23, 2.21
Cn-22
Speed Coincidence Bandwidth
0.1 Hz
0.0 - 25.5
2.0
2.23, 2.21
Cn-23
Carrier Frequency Upper Limit
0.1 kHz
0.4 - 15.0
See Note 3
2.36
Cn-24
Carrier Frequency Lower Limit
0.1 kHz
0.4 - 15.0
See Note 3
2.36
Cn-25
Frequency Proportion Gain
1
0 - 99
0
2.36
Cn-26
Overtorque Detection Level
1 %
30 - 200
160
2.18, 2.22
Cn-27
Overtorque Detection Time
0.1 s
0.0 - 25.5
0.1
2.22
Cn-28
Stall Prevention Level During
1 %
30 - 200
170
2.29
Accel (Constant Torque Region)
Cn-29
Stall Prevention Limit During
1 %
30 - 200
50
2.29
Accel (Constant HP Region)
Cn-30
Stall Prevention Level at Set
1 %
30 - 200
160
2.29
Frequency
Cn-31
Motor-to-Motor Cable
0.001
1 0.000 - 65.535
See Note 3
– –
Resistance
Cn-32
Torque Compensation Iron
1 W
0 - 65535
See Note 3
– –
Loss
Cn-33
Torque Compensation Limiter
1 V
0 - 50
(230V)
See Note 3
– –
0 - 100
(460V)
Cn-34
Motor No-load Current
1 %
0 - 99
30
2.35
See Note 2
Cn-35
Slip Compensation Primary
0.1 s
0.0 - 25.5
2.0
2.35
Delay Time
Cn-36
No. of Auto-Restart Attempts
1
0 - 10
0
2.5A
Table A1-4. Control Constants (Cn-XX) - Continued
CONSTANT
INCRE- SETTING
FACTORY
USER
PARA.
NUMBER
DATA NAME
MENT
RANGE
SETTING SETTING
REF.