2.24 REMOTE/LOCAL AND REFERENCE SELECTION Continued
Mode 2 (Memory, Auto, Manual) uses Auto, Manual and An-03 thru An-09.
The input commands at terminals 5 thru 8 are
binary coded to select the appropriate reference
command, where Auto is selected by binary zero
and An-09 (Jog) is selected by binary 8. For
example, if the value in An-04 is the desired
frequency reference, enter 0011 at terminals 5
thru 8. As a standard, the right-most bit and
terminal 5 are the LSB.
Sn-04 = remote operation.
Sn-15 = frequency reference select 1 at
terminal 5 (Auto/Manual).
Sn-16 = frequency reference select 2 at
terminal 6.
Sn 17 = frequency reference select 3 at
terminal 7.
Sn-18 = JOG reference select at terminal 8.
Sn-19 = manual reference at terminal 16.
2-WIRE CONTROL
3-WIRE CONTROL
Sn-04 = X X X
0
Sn-04 = X X X
0
Sn-15 =
03
Sn-15 =
00
Sn-16 =
04
Sn-16 =
03
Sn-17 =
05
Sn-17 =
04
Sn-18 =
06
Sn-18 =
06
Sn-19 =
00
Sn-19 =
00
GPD 503
5 (Sn-15)
6 (Sn-16)
7 (Sn-17)
8 (Sn-18)
F000.0
Freq.
External Terminal
Ref.
8
7
6
5
Auto
0
0
0
■
Manual
0
0
1
■
(Multi-func.)
An-03
0
1
0
■
An-04
0
1
1
■
An-09
1
X
X
■
Freq.
External Terminal
Ref.
8
7
6
5
Freq.
External Terminal
Ref.
8
7
6
5
Auto
0
0
0
0
Manual
0
0
0
1
(Multi-func.)
An-03
0
0
1
0
An-04
0
0
1
1
An-05
0
1
0
0
An-06
0
1
0
1
An-07
0
1
1
0
An-08
0
1
1
1
An-09
1
X
X
X
Freq.
External Terminal
Ref.
8
7
6
5
1 = Closed; 0 = Open;
X = No effect;
■
= FWD/REV
2-36.2