Measurement Computing Analyzer488 User Manual
Page 114

Section 4
Serial Controller
4.20
TRIGGER
The event message 'TRIGGER' is returned to the serial host when the
Analyzer488 trigger circuitry has found the trigger point. This event
is edge sensitive.
RECORD
The event message 'RECORD' is returned to the serial host when the
Analyzer488 recording sequence is finished. This event is edge
sensitive.
STEP
The event message 'STEP' is returned to the serial host when the bus
is ready for a source (talker) or acceptor (listener) handshake. This
event is edge sensitive.
MODE
any
BUS STATES
None
QUERY
String of events in the following format:
RESPONSE
ARM SRQ TRIGGER STEP RECORD
EXAMPLES
100 PRINT#1,"ARM SRQ"
Enable SRQ Condition
110 T = TIMER
110 IF LOC(1) THEN PRINT INPUT$(LOC(1),1);
120 IF TIMER - T < 5 GOTO 110
SRQ message will be received and printed if an SRQ occurs within
5 seconds after receipt of the ARM command.
PRINT #1,"ARM SRQ STEP"
Arm SRQ and STEP.
PRINT #1,"ARM?"
Query armed status.
INPUT #1, A$
Get response.
PRINT A$
Display results
The returned string would be:
'ARM SRQ STEP'
Refer to the demonstration program listed in appendix F for further examples of
the ARM command.