16 device data, fieldbus and communication module, Device data, fieldbus and communication module – Pilz PNOZ m B0 User Manual
Page 93

Modbus/TCP
Operating Manual PNOZmulti 2 Communication Interfaces
1002971EN02
93
6.4.16
Device data, fieldbus and communication module
The table below describes the Modbus/TCP data areas containing the static device data for
the fieldbus module and communication module.
Data area for fieldbus module
Register
(3x)
Coil/
Discrete Input
(1x)
Content
8624
137991 … 137984
Fieldbus module, product number (hex)
e.g.:772 132 = 0x000BC824 hex
}
8624 = 0x000B
}
8624 = 0xC824
137999 … 137992
8625
138007 … 138000
138015 … 138008
8626
138023 … 138016
Fieldbus module, serial number (hex)
e.g.: 123456
}
8626 = 0x0001,
}
8627 = 0x E240
138031 … 138024
8627
138039 … 138032
138047 … 138040
8628
138055 … 138048
Righthand fieldbus module, device type
138063 … 138056
8629
138071 … 138064
Fieldbus module, device version (hex)
138079 … 138072
8630
138087 … 138080
Fieldbus module, Firmware Version A
138095 … 138088
8631
138103 … 138096
Fieldbus module, Firmware Version B
138111 … 138104
8632
138119 … 138112
Fieldbus module, check sum of Firmware Version A
138127 … 138120
8633
138135 … 138128
Fieldbus module, check sum of Firmware Version B
138143 … 138136
8634
…
8641
138271 … 138144
Reserved