2 access to table segments, 3 led status, 4 diagnostic data pnoz m es profibus – Pilz PNOZ m B0 User Manual

Page 19: Access to table segments, Led status, Diagnostic data pnoz m es profibus

background image

Fieldbus Modules

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

19

4.2.2

Access to table segments

The data in the 

Tables [

 101]

 can be requested via the following objects.

Input data

The Master requests a table segment in the form:

Description

Input data from PNOZmulti 2

Table and segment number

2 Input Bytes

Output data

The PNOZmulti 2 replies in the form:

Description

Output data from PNOZmulti 2

Table and segment number + 13 Byte payload

15 Output Bytes

A detailed description is available in the chapter entitled 

Access to table segments [

 15]

.

4.2.3

LED status

The LED status of the PNOZmulti 2 can be requested directly via the following object.

Description

Output data from PNOZmulti 2

LED status

1 Output Byte

}

Bit 0 = 1: LED OFAULT is lit or flashes

}

Bit 1 = 1: LED IFAULT is lit or flashes

}

Bit 2 = 1: LED FAULT is lit or flashes

}

Bit 3 = 1: LED DIAG is lit or flashes

}

Bit 4 = 1: LED RUN is lit

}

Bit 5­7: Reserved

4.2.4

Diagnostic data PNOZ m ES Profibus

These bits contain the diagnostic data

Un­
it_Diag_Bit

Content

00

RUN, base unit is in RUN condition

01

STOP, base unit is in STOP condition

02

Base unit was stopped by the Configurator

03

Reserved

04

External error

05

Internal error

06

External error on the inputs