13 device data, base unit, Device data, base unit – Pilz PNOZ m B0 User Manual
Page 83

Modbus/TCP
Operating Manual PNOZmulti 2 Communication Interfaces
1002971EN02
83
Register
(3x)
Discrete Input
(1x)
Content
4117
65879 … 65872
10th character
65887 … 65880
4118
65895 … 65888
11th character
65903 … 65896
4119
65911 … 65904
12th character
65919 … 65912
4120
65927 … 65920
13th character
65935 … 65928
4121
65943 … 65936
14th character
65951 … 65944
4122
65959 … 65952
15th character
65967 … 65960
4123
65975 … 65968
16th character
65983 … 65976
4124
65991 … 65984
End of character string (identified by "FFFF")
65999 … 65992
4125
66007 … 66000
Reserved
66015 … 66008
6.4.13
Device data, base unit
The table below describes the Modbus/TCP data areas containing the base unit's device
data. The data was defined in the PNOZmulti Configurator.
Relevant areas for the data are defined in the Modbus/TCP data areas Discrete Inputs (1x)
and Input Register (3x). Read access is available to these data areas.
Register
(3x)
Discrete Input
(1x)
Content
8192
131079 … 131072
Product number
Example: 772 100 = 0x000BC804 hex
}
8192 = 0x000B
}
8193 = 0xC804
131087 … 131080
8193
131095 … 131088
131103 … 131096
8194
131111 … 131104
Serial number, example: 123 456: 0001E240
hex.
}
8194 = 0x0001,
}
8195 = 0xE240
131119 … 131112
8195
131127 … 131120
131135 … 131128
8196
131143 … 131136
Device type
131151 … 131144