13 device data, base unit, Device data, base unit – Pilz PNOZ m B0 User Manual

Page 83

background image

Modbus/TCP

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

83

Register

(3x)

Discrete Input

(1x)

Content

4117

65879 … 65872

10th character

65887 … 65880

4118

65895 … 65888

11th character

65903 … 65896

4119

65911 … 65904

12th character

65919 … 65912

4120

65927 … 65920

13th character

65935 … 65928

4121

65943 … 65936

14th character

65951 … 65944

4122

65959 … 65952

15th character

65967 … 65960

4123

65975 … 65968

16th character

65983 … 65976

4124

65991 … 65984

End of character string (identified by "FFFF")

65999 … 65992

4125

66007 … 66000

Reserved

66015 … 66008

6.4.13

Device data, base unit

The table below describes the Modbus/TCP data areas containing the base unit's device
data. The data was defined in the PNOZmulti Configurator.

Relevant areas for the data are defined in the Modbus/TCP data areas Discrete Inputs (1x)
and Input Register (3x). Read access is available to these data areas.

Register

(3x)

Discrete Input

(1x)

Content

8192

131079 … 131072

Product number

Example: 772 100 = 0x000BC804 hex

}

8192 = 0x000B

}

8193 = 0xC804

131087 … 131080

8193

131095 … 131088

131103 … 131096

8194

131111 … 131104

Serial number, example: 123 456: 0001E240
hex.

}

8194 = 0x0001,

}

8195 = 0xE240

131119 … 131112

8195

131127 … 131120

131135 … 131128

8196

131143 … 131136

Device type

131151 … 131144