beautypg.com

3 control byte (byte 5), Control byte (byte 5) – Pilz PNOZ m B0 User Manual

Page 42

background image

Communication modules

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

42

Output Byte

Content

12

o103 to o96

13

o111 to o104

14

o119 to o112

15

o127 to o120

16

LED status

17

Table number

18

Segment number

19

Payload Byte 0

20

Payload Byte 1

21

Payload Byte 2

22

Payload Byte 3

23

Payload Byte 4

24

Payload Byte 5

25

Payload Byte 6

26

Payload Byte 7

27

Payload Byte 8

28

Payload Byte 9

29

Payload Byte 10

30

Payload Byte 11

31

Payload Byte 12

The content of the tables and segments is described in detail in the Appendix 

Appendix [

 101]

.

5.7.6.3

Control Byte (Byte 5)

Bit 0 … 2 of the Control Byte contain a watchdog function.

If no virtual inputs are sent by a communications partner within the defined watchdog time
(watchdog timeout), the PNOZmulti sets the virtual inputs to "0".

Control Byte 5:

Read/
Write

Delayed
Re­
sponse

Error
Message

Reserved Reserved W­Timer

Bit 2

W­Timer

Bit 1

W­Timer

Bit 0

}

Bit 0 ­ 2: Watchdog Timeout