beautypg.com

2 pnoz m es profibus, 1 input and output data, Pnoz m es profibus – Pilz PNOZ m B0 User Manual

Page 18: Input and output data

background image

Fieldbus Modules

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

18

Master

Fieldbus module

24

1

0

17

18

19

31

17

18

19

31

255

0

X

X

24

4.2

PNOZ m ES Profibus

4.2.1

Input and output data

Virtual inputs and outputs can be requested or set directly via the following objects. Each
element can be selected individually in the master control system, e.g. virtual inputs i0­31.
The data width is also established this way.

Input data

The Master writes to the virtual inputs of the PNOZmulti 2.

Description

Input data from PNOZmulti 2

Virtual inputs i0 – i31

4 Input Bytes

Virtual inputs i32 – i63

4 Input Bytes

Virtual inputs i64 – i95

4 Input Bytes

Virtual inputs i96 – i127

4 Input Bytes

Output data

The Master reads the virtual outputs of the PNOZmulti 2.

Description

Output data from PNOZmulti 2

Virtual outputs o0 – o31

4 Output Bytes

Virtual outputs o32 – o63

4 Output Bytes

Virtual outputs o64 – o95

4 Output Bytes

Virtual outputs o96 – o127

4 Output Bytes