Modbus/TCP

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

46

6.3

Modbus/TCP with PNOZmulti 2

An interface for communication via Modbus/TCP is provided on the PNOZmulti 2 through
the communication module PNOZ m ES ETH.

A PNOZ m ES ETH can manage a max. of 8 Modbus/TCP connections. The PNOZmulti 2
is always the Server in a connection. The connection Clients may be various devices, e.g.
PC (PNOZmulti Configurator), control system, display unit. They can access the configur­
able control system PNOZmulti 2 simultaneously.

The virtual I/Os plus all the information that is polled during fieldbus communication are
contained in data areas. The data is accessed directly. It's no longer necessary to switch
via table/segment.

PC
192.168.1.60

PMI
192.168.1.10

PSSu-System
192.168.1.100

PNOZ m B0 +
PNOZ m ES ETH
192.168.1.110

PNOZ mm0.1p +
PNOZ mmc1p ETH
192.168.1.2

PNOZ m1p ETH
192.168.1.1

The configurations required for Modbus/TCP are fully pre­configured in the PNOZmulti 2
operating system. All that's necessary in the PNOZmulti Configurator is to activate the vir­
tual inputs and outputs (see PNOZmulti Configurator's online help, under "Display and edit
module selection").

On a configurable control system PNOZmulti 2 , port number "502" is fixed as the default
for data exchange via a Modbus/TCP connection. It is not displayed in the PNOZmulti Con­
figurator and cannot be modified.