Modbus/TCP
Operating Manual PNOZmulti 2 Communication Interfaces
1002971EN02
51
The table below describes the Modbus/TCP data areas for the watchdog.
A relevant area for the watchdog is defined in each Modbus/TCP data area (Coils (0x), Dis
crete Inputs (1x), Input Register (3x), Holding Register (4x)). Read/write access will depend
on the Modbus/TCP data area.
Register
(3x, 4x)
Coil/
Discrete Input
(0x, 1x)
Content
High Byte
Low Byte
255
4095...4080
Control Register
See table below
High Byte WDTrig
ger
Error Mes
sage
Reserved
Reserved
Reserved
WTimer
Bit 2
WTimer
Bit 1
WTimer
Bit 0
Low Byte Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Bit 15 "Watchdog Trigger": The watchdog can be triggered by setting Bit 15 constantly to
"1", or by a Client writing in the input area of the 128 inputs. The state of the bit when read
ing is undefined. A 1 or a 0 can be read.
Bit 14 "Error Message": If this bit is set, an error stack entry is generated when the watch
dog is triggered.
Bit 10 … 8 "WD Timer": If the set time for the watchdog is set, then Bit 15 must be set, or
become set, at the same time.
Watchdog Timer
Bit 2
Watchdog Timer
Bit 1
Watchdog Timer
Bit 0
Watchdog Time
0
0
0
Timer deactivated
0
0
1
100 ms
0
1
0
200 ms
0
1
1
500 ms
1
0
0
1 s
1
0
1
3 s
1
1
0
5 s
1
1
1
10 s
INFORMATION
To check whether the watchdog has been triggered, set a virtual input per
manently to "1".
If the corresponding input in the PNOZmulti 2 is "0", then the watchdog has
been triggered.