beautypg.com

Pilz PNOZ m B0 User Manual

Page 123

background image

Appendix

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

123

8.1.11

Table 93 ­ Device data, fieldbus and communication module

Table 93 contains

}

For a connected fieldbus module: the device data of the fieldbus module in segments 0
… 2, each with 13 Bytes

}

For a connected external communication module: the device data of the external com­
munication module in segments 3 … 5, each with 13 Bytes.

Segment

Byte

Content

0

0 … 3

Product number (hex), fieldbus module

e.g.: 772 132 = 0x000BC824 hex

}

Byte 0 = 0x00

}

Byte 1 = 0x 0B

}

Byte 2 = 0xC8

}

Byte 3 = 0x 24

4 … 7

Serial number (hex), fieldbus module

e.g. 123 456: 0001E240 hex.

}

Byte 4 and 5 = 0001,

}

Byte 6 and 7 = E240

8, 9

Device type, fieldbus module

}

PROFIBUS: 0x0001

}

CANopen: 0x0020

}

PROFINET: 0x0084

}

EtherCAT: 0x0087

}

Powerlink: 0x0098

10, 11

Device version (hex), fieldbus module

12

Reserved

1

0, 1

Firmware Version A of fieldbus module

2, 3

Reserved

4, 5

Check sum of Firmware A of fieldbus module

6 … 12

Reserved

2

0 … 12

Reserved

3

0 … 3

Product number (hex), external communication module

4 … 7

Serial number (hex), external communication module

8, 9

Device type, external communication module

10, 11

Device version (hex), external communication module

12

Reserved

4

0, 1

Firmware Version A of external communication module

2, 3

Reserved

4, 5

Check sum of Firmware A of external communication module

6 … 12

Reserved