8.1.11
Table 93 Device data, fieldbus and communication module
Table 93 contains
}
For a connected fieldbus module: the device data of the fieldbus module in segments 0
… 2, each with 13 Bytes
}
For a connected external communication module: the device data of the external com
munication module in segments 3 … 5, each with 13 Bytes.
Segment
Byte
Content
0
0 … 3
Product number (hex), fieldbus module
e.g.: 772 132 = 0x000BC824 hex
}
Byte 0 = 0x00
}
Byte 1 = 0x 0B
}
Byte 2 = 0xC8
}
Byte 3 = 0x 24
4 … 7
Serial number (hex), fieldbus module
e.g. 123 456: 0001E240 hex.
}
Byte 4 and 5 = 0001,
}
Byte 6 and 7 = E240
8, 9
Device type, fieldbus module
}
PROFIBUS: 0x0001
}
CANopen: 0x0020
}
PROFINET: 0x0084
}
EtherCAT: 0x0087
}
Powerlink: 0x0098
10, 11
Device version (hex), fieldbus module
12
Reserved
1
0, 1
Firmware Version A of fieldbus module
2, 3
Reserved
4, 5
Check sum of Firmware A of fieldbus module
6 … 12
Reserved
2
0 … 12
Reserved
3
0 … 3
Product number (hex), external communication module
4 … 7
Serial number (hex), external communication module
8, 9
Device type, external communication module
10, 11
Device version (hex), external communication module
12
Reserved
4
0, 1
Firmware Version A of external communication module
2, 3
Reserved
4, 5
Check sum of Firmware A of external communication module
6 … 12
Reserved