background image

Modbus/TCP

Operating Manual PNOZmulti 2 Communication Interfaces
1002971­EN­02

50

Register

(3x, 4x)

Coil/

Discrete Input

(0x, 1x)

Content

High Byte

Low Byte

0

15... 0

State of virtual inputs
0...15

i15…i8

i7…i0

1

31... 16

State of virtual inputs
16...31

i31…i24

i23…i16

2

47...32

State of virtual inputs
32...47

i47…i40

i39…i32

3

63...48

State of virtual inputs
48...63

i63…i56

i55…i48

4

79... 64

State of virtual inputs
64...79

i79…i72

i71…i64

5

95...80

State of virtual inputs
80...95

i95…i88

i87…i80

6

111...96

State of virtual inputs
96...111

i111…i104

i103…i96

7

127...112

State of virtual inputs
112...127

i127…i120

i119…i112

The table below describes the Modbus/TCP data areas that contain the states of the virtual
outputs of the PNOZmulti 2.

Relevant areas for the data are defined in the Modbus/TCP data areas Discrete Inputs (1x)
and Input Register (3x). Read access is available to these data areas.

Register

(3x)

Discrete Input

(1x)

Content

High Byte

Low Byte

512

8207...8192

State of virtual outputs
0...15

o15…o8

o7…o0

513

8223...8208

State of virtual outputs
16...31

o31…o24

o23…o16

514

8239...8224

State of virtual outputs
32...47

o47…o40

o39…o32

515

8255...8240

State of virtual outputs
48...63

o63…o56

o55…o48

516

8271...8256

State of virtual outputs
64...79

o79…o72

o71…o64

517

8287...8272

State of virtual outputs
80...95

o95…o88

o87…o80

518

8303...8288

State of virtual outputs
96...111

o111…o104

o103…o96

519

8319...8304

State of virtual outputs
112...127

o127…o120

o119…o112

A watchdog can be activated in Control Register 255. 
If no input bits are set by a Modbus/TCP subscriber within the preset time, the PNOZmulti 2