2 operation time log, 3 sensor log, Operation time log – AERCO C-More Controls Manual June 2010 User Manual
Page 89: Sensor log, C-more controller for benchmark, innovation & kc

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 89 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
Table 7-1: Sample Fault Log Display
No.
Fault Message
Cycle Date
Time
0
Direct Drive Signal Fault
609 1/10/02
8:42am
1
Low Gas Pressure
366 7/04/01
5:29pm
2
Loss of Power
0 1/01/01
11:50am
7.5.2
Operation Time Log
The Operation Time Log consists of a string of ASCII records stored in non-volatile memory
within the C-More Control Panel. Events such as power-up, ignition and turn-off are time
stamped. Data logged while the unit is running are run-length encoded. Data is logged or the
run-length incremented every 30 seconds. For a new run record to be logged, the fire rate or
flame strength must change by more than 5%, or the run mode must change. At steady-state,
the run-length is allowed to reach a maximum of 30 minutes before the record is logged. This
means that no more than 30 minutes of data can be lost if the unit loses power. Table 7-2
shows a sample Operation Time Log for a boiler: The Operation Time Log can only be
accessed through the RS232 interface using a laptop or other terminal device. Ten operation
time records are displayed for each T command entry. The operation time log can be cleared
ONLY by factory authorized personnel using the Clear Log option in the Factory menu.
NOTE
The Sensor (S) Log can store up to 1200 records. Therefore, to
view the most recently logged record, enter “S” followed by 0
(zero) and then press Enter (i.e. S0
records in reverse chronological order, enter S and press Enter.
To go back 200 or 700 records, enter S200 or S700, etc. and
press Enter.
Table 7-2: Sample Operation Time Log Display
Status
Valve
Position
Flame
Run Length
Date
Time
Off, Direct Drive
0
0
8
1/15/02
2:35pm
Run, Direct Drive
38
100
34
1/15/02
2:27pm
Run, Direct Drive
31
100
30
1/15/02
1:53am
Run, Direct Drive
35
100
2
1/15/02
1:23pm
Run, Direct Drive
29
100
0
1/15/02
1:21pm
Ignition
0
0
0
1/15/02
1:20pm
Off, Switch
0
0
35
1/15/02
12:30pm
Run, Manual
40
100
0
1/15/02
11:55am
Ignition
0
0
0
1/15/02
11:55am
Power-up
0
0
0
1/15/02
11:50am
7.5.3
Sensor Log
The sensor values can be logged at a different rate if needed by setting the Sensor Log Interval
in the Diagnostics Menu. The log interval can vary from once every minute to once every day.
Table 7-3 shows a sample Sensor Log every 5 minutes for a boiler running in Constant Setpoint
mode.