3.2 FACTORY DEFAULTS
The factory default values for each menu item are summarized in Table 3-2.
Table 3-2: Default Settings
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
BMK Boiler LN
Unit Size
2.0 MBTU
Fuel Type
Natural Gas
Boiler Mode
(If Unit Type = Boiler)
Constant Setpoint
Heater Mode
(If Unit Type = Water Heater)
Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Temp Hi Limit
210°F
Max Valve Position
100%
Pump Delay Timer (If Unit Type = Boiler)
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
Analog Output
Valve Position 0-10V
Low Fire Timer
2 sec