BST Setpoint Hi
Limit
The BST Setpoint Hi Limit is the maximum allowable setpoint
setting.
30117
BST Setpoint Lo
Limit
The BST Setpoint Lo Limit is the minimum allowable setpoint
setting.
30118
BST Temp Hi
Limit
The critical temperature limit above which the BST Master will
alarm and lower the Fire Rate of all boilers.
30119
BST Setpoint
Mode
The operating mode of the BST Master – Constant Setpoint,
Remote Setpoint or Outdoor Reset.
40053
BST Timeout
If the BST system has not written to the SSD in 15 seconds,
this register will read as one.
Reading individual Boilers or Water Heaters:
Unit Addr
Modbus Address
1
30300 to 30349
2
30400 to 30449
3
30500 to 30549
4
30600 to 30649
5
30700 to 30749
6
30800 to 30849
7
30900 to 30949
8
31000 to 31049
Below are examples for Boiler Address 1:
BAS
Register
Use
Description
30300
comm_addr
Modbus address of unit.
30301
unit_status
status (0=Disabled, 1=Standby, 2=Manual, 3=Remote,
4=Auto, 5=Fault).
30302
fault_code
Fault codes 0-74 matching the normal unit fault codes. See
GF-XXX for meaning (0 to 74)
30303
outlet_temp
Outlet temp sensor in degrees or counts
.
30304
ffwd_temp
Feed forward temp sensor in degrees or counts.
Used as Header Temp Sensor in Master unit.
30305
inlet_temp
inlet water temp sensor in degrees or counts.
30306
exhaust_temp
Exhaust temp sensor in degrees or counts.
30307
air_temp
Air temp sensor in degrees or counts.
30308
flame_strength
Measured flame strength of unit while it is running.
30309
fire_rate_in
Valve position signal sent to the boiler.
30310
fire_rate_out
Measured valve position.
30311
unit_type
The type of the unit. C_mnue.h
30312
unit_size
see A_BMSG.H for enum of sizes.
30313
comm_err_count
count of errors for this unit (0 if unit functioning).
30314
network_remote_setpt temperature (in counts) unit is set for when in HST mode.
30315
run_cycles
upper 16 bits of run cycles.
30316
run_cycles
lower 16 bits of run cycles.
30317
run_hours
upper 16 bits of run hours.
30318
run_hours
lower 16 bits of run hours.