BST Setpoint Hi
Limit

The BST Setpoint Hi Limit is the maximum allowable setpoint
setting.

30117

BST Setpoint Lo
Limit

The BST Setpoint Lo Limit is the minimum allowable setpoint
setting.

30118

BST Temp Hi
Limit

The critical temperature limit above which the BST Master will
alarm and lower the Fire Rate of all boilers.

30119

BST Setpoint
Mode

The operating mode of the BST Master – Constant Setpoint,
Remote Setpoint or Outdoor Reset.

40053

BST Timeout

If the BST system has not written to the SSD in 15 seconds,
this register will read as one.


Reading individual Boilers or Water Heaters:

Unit Addr

Modbus Address

1

30300 to 30349

2

30400 to 30449

3

30500 to 30549

4

30600 to 30649

5

30700 to 30749

6

30800 to 30849

7

30900 to 30949

8

31000 to 31049


Below are examples for Boiler Address 1:

BAS
Register

Use

Description

30300

comm_addr

Modbus address of unit.

30301

unit_status

status (0=Disabled, 1=Standby, 2=Manual, 3=Remote,
4=Auto, 5=Fault).

30302

fault_code

Fault codes 0-74 matching the normal unit fault codes. See
GF-XXX for meaning (0 to 74)

30303

outlet_temp

Outlet temp sensor in degrees or counts

.

30304

ffwd_temp

Feed forward temp sensor in degrees or counts.
Used as Header Temp Sensor in Master unit.

30305

inlet_temp

inlet water temp sensor in degrees or counts.

30306

exhaust_temp

Exhaust temp sensor in degrees or counts.

30307

air_temp

Air temp sensor in degrees or counts.

30308

flame_strength

Measured flame strength of unit while it is running.

30309

fire_rate_in

Valve position signal sent to the boiler.

30310

fire_rate_out

Measured valve position.

30311

unit_type

The type of the unit. C_mnue.h

30312

unit_size

see A_BMSG.H for enum of sizes.

30313

comm_err_count

count of errors for this unit (0 if unit functioning).

30314

network_remote_setpt temperature (in counts) unit is set for when in HST mode.

30315

run_cycles

upper 16 bits of run cycles.

30316

run_cycles

lower 16 bits of run cycles.

30317

run_hours

upper 16 bits of run hours.

30318

run_hours

lower 16 bits of run hours.