C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 25 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

WHM Setpoint

60ºF

195ºF

130ºF

WHM Setpoint

60ºF

195ºF

130ºF

Next On VP

16%

100%

75%

Next Off VP

16%

100%

35%

Lead/Lag Hours

25

225

72

WHM Upload Timer

0

9999

0

Setback Setpoint

40ºF

220ºF

130ºF

Setback Start

12:00 am

11:59 pm

12:00 am

Setback End

12:00 am

11:59 pm

12:00 am

Table 2-4: WHM Menu - Continued

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Password Level 2 (includes all of the previous options, plus the following:)

WHM Auto Mstr

Yes or No

No

WHM Auto Timer

10 sec.

120 sec.

30 sec.

WHM Min Addr

1

8

1

WHM Max Addr

1

8

8

WHM On Delay

30 sec.

300 sec.

60 sec.

WHM Off Delay

30 sec.

300 sec.

60 sec.

WHM Min Units

1

8

1

WHM Warmup Time

0 sec

300 sec.

30 sec.

WHM On Timeout

15 sec.

300 sec.

30 sec.

WHM Valve State

0 (closed) or 1 (open)

read only

WHM Units (1 – 8)

0 = Off

1 = On

- = Off-Line

* = Not available (fault, etc.)

A = Lead On

B = Lag On

a = Lead Off

b = Lag Off