C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 25 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
WHM Setpoint
60ºF
195ºF
130ºF
WHM Setpoint
60ºF
195ºF
130ºF
Next On VP
16%
100%
75%
Next Off VP
16%
100%
35%
Lead/Lag Hours
25
225
72
WHM Upload Timer
0
9999
0
Setback Setpoint
40ºF
220ºF
130ºF
Setback Start
12:00 am
11:59 pm
12:00 am
Setback End
12:00 am
11:59 pm
12:00 am
Table 2-4: WHM Menu - Continued
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Password Level 2 (includes all of the previous options, plus the following:)
WHM Auto Mstr
Yes or No
No
WHM Auto Timer
10 sec.
120 sec.
30 sec.
WHM Min Addr
1
8
1
WHM Max Addr
1
8
8
WHM On Delay
30 sec.
300 sec.
60 sec.
WHM Off Delay
30 sec.
300 sec.
60 sec.
WHM Min Units
1
8
1
WHM Warmup Time
0 sec
300 sec.
30 sec.
WHM On Timeout
15 sec.
300 sec.
30 sec.
WHM Valve State
0 (closed) or 1 (open)
read only
WHM Units (1 – 8)
0 = Off
1 = On
- = Off-Line
* = Not available (fault, etc.)
A = Lead On
B = Lag On
a = Lead Off
b = Lag Off