beautypg.com

3 demand offset function, Demand offset function, C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual

Page 46

background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 46 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

Setpoint

Setpoint + Deadband High

Outlet

Temp

Figure 3-2: Valve Position Less Than HI DB Setpt EN

If the unit Valve Position is less than the HI_DB_SETPT_EN setting, The C-More will aim to
bring the Outlet Temperature to the Setpoint + Deadband_High value. This will delay shutting
down the unit, thus decreasing “on/off cycling”.

Setpoint

Setpoint + Deadband High

Outlet

Temp

Figure 3-3: Valve Position

≥ HI DB Setpt EN

3.1.3

Demand Offset Function

The Demand Offset entry in the Configuration Menu allows delay of re-ignition of the unit while
maintaining proper temperature control.

In normal operation, the unit will re-ignite when the PID Loop calculates that the required Valve
Position is greater than the Start_Level value.

Whenever the Demand_Offset value is Non Zero, the unit will re-ignite when the PID Loop
calculates that the required Valve Position is greater than the Start_Level value AND the Outlet_
Temperature drops below the Setpoint minus the Demand_Offset value.

This will delay the unit re-ignition by waiting for the Outlet Temperature to decay.

The default value for Demand Offset is 10.

When set to zero (0), the PID Turn On Delay is also disabled.

This manual is related to the following products: