Table 3-1: Menu Item Descriptions - Continued

MENU LEVEL & OPTION

DESCRIPTION

Calibration Menu (Continued)

SKIP FEATURE:

The following three menu items below embody a feature that allows the user to define a Fire
Zone the C-More will avoid. In the rare instance when a boiler emits an objectionable noise at a
certain Fire Rate and no other remedy solves the problem, a Fire Rate skip zone may be defined
to command the C-More to Skip-Over the defined Fire Rate.
Skip Range CNTR

Defines the Center (Fire Rate) of the skip band.

Skip Range Span

Defines the + and – band of the Skip Zone Size. 0 = disabled.

Skip Speed

Defines the speed (Seconds/Fire Rate) at which the band will be
skipped.

Skip Speed

Defines the speed (Seconds/Fire Rate) at which the band will be
skipped.

O2 Settings: The following two menu items allow calibration of the Oxygen readings.

O2 Gain

Range = 920 to 1126. Default = 1024 (Unity Gain, No Mods)

O2 Offset

Range = -3.0 to +3.0. Default = 1.0.

Temperature Channel Offset:

The following six menu items embody the feature, which allows the user to field calibrate all six
temperature channels by entering an offset corresponding to the desired temperature channel.
FFWD Temp Offset

Range = -20ºF to +20ºF. Default = 0º

Inlet Air Offset

Range = -20ºF to +20ºF .

Exhst Tmp Ofset

Range = -20ºFto +20ºF .

Inlet Wtr Offset

Range = -20ºF to +20ºF.

Outdr Air Offset

Range = -20ºF to +20ºF .

Outlet Wtr Offset

Range = -20ºF to +20ºF .

0 – 10V Out Test