Table 3-1: Menu Item Descriptions - Continued

MENU LEVEL & OPTION

DESCRIPTION

Configuration Menu

Internal Setpoint

Allows internal setpoint to be set (40°F to 240°F). Default is 130°F.

Unit Type

Allows selection of: KC Boiler, KC Boiler LN, BMK Boiler Std,
BMK Boiler LN, BMK Blr Std Dual, BMK Blr LN Dual, KC Water
Heater, KC Wtr Heater LN, Innovation WH

Unit Size

Sets unit size from 500 MBH to 6000 MBH.
Default is 2000 MBH.

Fuel Type

Allows selection of fuel type used (Natural Gas or Propane. Default
is Natural Gas.
When selecting “Natural Gas” as the Fuel Type.
(a) The ignition Trial Time is set to 4 seconds.
(b) The “Natural Gas” parameters will be enabled while running to

ensure proper combustion.

(c) The “Natural Gas” parameters will be used when performing

Combustion Calibration.

When selecting “Propane” as the Fuel Type.
(a) The Ignition Trial Time is set to 4 seconds.
(b) The “Propane” parameters will be enabled while running to

ensure proper combustion.

(c) The “Propane” parameters will be used when performing

Combustion Calibration.

Boiler Mode
(If Unit Type = Boiler)

Allows selection of: Constant Setpoint, Remote Setpoint, Direct
Drive, Combination, or Outdoor Reset Mode. Default is Constant
Setpoint Mode.

Heater Mode
(If Unit Type = Water
Heater)

Allows selection of Constant Setpoint or Remote Setpoint Mode.
Default is Constant Setpoint Mode.

Remote Signal
(If Mode = Remote
Setpoint,
Direct Drive or
Combination)

Used to set the type of external signal which will be used when
operating in the Remote Setpoint, Direct Drive or Combination
Mode. Default is 4 to 20 mA / 1 to 5V.

Bldg Ref Temp
(If Boiler Mode = Outdoor
Reset)

Allows the building reference temperature to be set when operating
a boiler in the Outdoor Reset Mode. Default is 70°F

Reset Ratio
(If Boiler Mode = Outdoor
Reset)

Permits setting of Reset Ratio when operating boiler in the Outdoor
Reset Mode. Reset Ratio is adjustable from 0.1 to 9.9. Default is
1.2.

Outdoor Sensor

Allows outdoor sensor function to be enabled or disabled. Default
is Disabled.