5 configuration menu, Configuration menu, C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual
Page 21

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 21 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
Table 2-2: Setup Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
Level 1 = 159
Level 2 = 6817
0
9999
0
Language
English
English
Time
12:00 am
11:59 pm
Date
01/01/00
12/31/99
Unit of Temp
Fahrenheit
Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400
4800
9600
19.2K
9600
OnAER Mode
Ethernet
SD Card
Ethernet
Min. Upload Timer
30
9999
0
Unit Alpha
A
Z
E
Unit Year
00
99
00
Unit Serial#
0000
9999
0000
Software Version
Read Only
Current
software
version is
displayed
2.5 CONFIGURATION MENU
The Configuration Menu shown in Table 2-3 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for
operation in the Constant Setpoint mode. The remaining options in this menu require the valid
password to be entered, prior to changing existing entries. This menu contains a number of
other configuration settings which may or may not be displayed, depending on the current
operating mode setting.