Table 4-2: Fault Messages - Continued

FAULT MESSAGE

FAULT DESCRIPTION

REMOTE SETPT

SIGNAL FAULT

The remote setpoint signal is not present or is out of range.

OUTDOOR TEMP

SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out of
range.

OUTLET TEMP

SENSOR FAULT

The temperature measured by the Outlet Sensor is out of range.

FFWD TEMP

SENSOR FAULT

The temperature measured by the Feed-Forward (FFWD) Sensor is
out of range.

HIGH WATER

TEMPERATURE

The temperature measured by the Outlet Sensor exceeded the
Temp Hi Limit setting.

LINE VOLTAGE

OUT OF PHASE

The High AC voltage is out of phase from the low AC voltage.

STEPPER MOTOR

FAILURE

The stepper motor failed to move the valve to the desired position.

MODBUS COMM

FAULT

The RS485 (Modbus) network information is not present or is
corrupted.

WAIT IGNITION RETRY

The unit is in Ignition Retry Mode. This is an informational
message.

WAIT FAULT PURGE

The unit is purging after a fault. This is an informational message.

WAIT RETRY PAUSE

The unit is pausing between ignition retries. This is an informational
message.

EXHAUST TEMP

SENSOR SHORT

The temperature measured by Exhaust temperature sensor reading
is out of range.

EXHAUST TEMP

SENSOR OPEN

The temperature measured by Exhaust temperature sensor reading
is out of range.

WARNING EXHAUST

TEMP HIGH

The exhaust temperature has exceeded the high Exhaust Temp
Limit. This is an informational warning.

EXHAUST TEMP HIGH

The temperature measured by the Exhaust temperature sensor is
out of range.

INLET WATER TEMP

SENSOR SHORT

The temperature measured by the inlet water temp sensor is out of
range.

INLET WATER TEMP

SENSOR OPEN

The temperature measured by the Inlet water temperature sensor is
out of range.

WARNING IN WTR TEMP

HIGH

This is a warning that the inlet water temperature has exceeded its
high limit.

WARNING IN WTR TEMP

LOW

This is a warning that the inlet water temperature is below the low
limit.

INLET GAS PRESS

SENSOR OPEN

The inlet gas pressure sensor is reading out of range.

GAS PLATE DP SENSOR

OPEN

Not in use.

O2 PERCENTAGE LOW

The O2 percentage is below its low limit for the fire rate.

O2 SENSOR

MALFUNCTION

The O2 sensor is reporting a fault condition.

WARNING O2 LEVEL

HIGH

The o2 percentage is above its high limit for the fire rate.

RECIRC PUMP FAILURE

For water heaters. A recirculation pump condition has been
detected. The inlet water temperature matches the FFWD
temperature during operation for a predetermined amount of time.

IGNITION MONITOR

Ignition time. For information only.

NO FLOW SAFETY

LOCKOUT

Not in use.