Table 3-1A: Descriptions Associated With Diagnostic Menu Warnings
EXHAUST TEMPERATURE WARNINGS
UNIT TYPE
VALUE
C-MORE RESPONSE
ALL
Open
Displays Fault, continues to run.
ALL
Short
Displays Fault, continues to run.
BMK Boiler LN
>= 300ºF
Displays alternating warning, continues to
run.
BMK Boiler LN
>= 500ºF
Displays Fault and Halts.
BMK Boiler
>= 385ºF
Displays alternating warning, continues to
run.
BMK Boiler
>= 500ºF
Displays Fault and Halts.
KC Boiler
KC Boiler LN
KC Water Heater
>= 475ºF
Displays alternating warning, continues to
run.
KC Boiler
KC Boiler LN
KC Water Heater
>= 500ºF
Displays Fault and Halts.
INLET WATER TEMPERATURE WARNINGS
UNIT TYPE
VALUE
C-MORE RESPONSE
ALL Boilers
Open
Displays Fault, continues to run.
ALL Boilers
Short
Displays Fault, continues to run.
ALL Water Heaters
Open
Displays Fault and Halts.
ALL Water Heaters
Short
Displays Fault and Halts.
BMK Boiler
BMK Boiler LN
>= 210ºF
Displays alternating warning, continues to
run.
KC Boiler
>= 230ºF
Displays alternating warning, continues to
run.
KC Water Heater
KC Water Heater
LN
>= 200ºF
Displays alternating warning, continues to
run.
ALL
< 20 Deg F
Displays Fault, continues to run.
SUPPLY GAS PRESSURE, GAS PLATE DP, INLET WATER FLOW WARNINGS
UNIT TYPE
VALUE
C-MORE RESPONSE
ALL
Open (<3.5 mA)
Displays Fault and Halts