C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 44 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

Table 3-1A: Descriptions Associated With Diagnostic Menu Warnings

EXHAUST TEMPERATURE WARNINGS

UNIT TYPE

VALUE

C-MORE RESPONSE

ALL

Open

Displays Fault, continues to run.

ALL

Short

Displays Fault, continues to run.

BMK Boiler LN

>= 300ºF

Displays alternating warning, continues to
run.

BMK Boiler LN

>= 500ºF

Displays Fault and Halts.

BMK Boiler

>= 385ºF

Displays alternating warning, continues to
run.

BMK Boiler

>= 500ºF

Displays Fault and Halts.

KC Boiler
KC Boiler LN
KC Water Heater

>= 475ºF

Displays alternating warning, continues to
run.

KC Boiler
KC Boiler LN
KC Water Heater

>= 500ºF

Displays Fault and Halts.

INLET WATER TEMPERATURE WARNINGS

UNIT TYPE

VALUE

C-MORE RESPONSE

ALL Boilers

Open

Displays Fault, continues to run.

ALL Boilers

Short

Displays Fault, continues to run.

ALL Water Heaters

Open

Displays Fault and Halts.

ALL Water Heaters

Short

Displays Fault and Halts.

BMK Boiler
BMK Boiler LN

>= 210ºF

Displays alternating warning, continues to
run.

KC Boiler

>= 230ºF

Displays alternating warning, continues to
run.

KC Water Heater
KC Water Heater
LN

>= 200ºF

Displays alternating warning, continues to
run.

ALL

< 20 Deg F

Displays Fault, continues to run.

SUPPLY GAS PRESSURE, GAS PLATE DP, INLET WATER FLOW WARNINGS

UNIT TYPE

VALUE

C-MORE RESPONSE

ALL

Open (<3.5 mA)

Displays Fault and Halts