CALIBRATION POINTS
Valve Position % Open

Default Voltage Settings


UNIT TYPE & SIZE


FUEL

18%

30%

40%

50%

70%

100%,

BMK LN CP 6000

Natural Gas

1.60v

3.00v

4.00v

5.00v

7.00v

10.00v

18%

30%

45%

65%

85%

100%

BMK LN CP 6000

Dual Fuel

Natural Gas

2.00v

2.00v

2.45v

3.70v

6.35v

8.50v

18%

30%

45%

65%

85%

100%

Propane

2.00v

2.00v

2.45v

3.70v

6.35v

8.50v

Table 3-2B: Combustion Cal Menu Default Settings (Version 3.08.xx)

CALIBRATION POINTS
Valve Position % Open

Default Voltage Settings


INN UNIT SIZE


FUEL

16%

20%

30%

40%

50%

60%

80%

100%

INN 600

Natural Gas

1.90v 2.05v 2.20v 2.50v 2.80v 3.00v 3.65v

4.40v

16%

20%

30%

40%

50%

60%

80%,

100%

INN 600

Propane

2.00v 2.50v 3.20v 3.50v 3.70v 3.80v 4.00v

4.10v

16%

20%

30%

40%

50%

60%

80%

100%

INN 800

Natural Gas

1.90v 2.00v 2.50v 3.10v 3.50v 3.85v 4.70v

5.45v

16%

20%

30%

40%

50%

60%

80%,

100%

INN 800

Propane

2.10v 3.00v 4.40v 4.50v 4.60v 4.70v 4.80v

5.00v

16%

20%

30%

40%

50%

60%

80%

100%

INN 1060

Natural Gas

1.90v 2.30v 2.80v 3.00v 3.60v 3.90v 4.80v

6.00v

16%

20%

30%

40%

50%

60%

80%,

100%

INN 1060

Propane

2.00v 2.70v 3.80v 4.00v 4.50v 4.90v 5.50v

6.25v

16%

20%

30%

40%

50%

60%

80%

100%

INN 1350

Natural Gas

1.90v 2.60v 4.20v 4.70v 5.00v 5.00v 5.50v

6.00v

16%

20%

30%

40%

50%

60%

80%,

100%

INN 1350

Propane

2.10v 2.30v 4.70v 5.00v 5.20v 5.40v 5.80v

6.25v