C-more controller for benchmark, innovation & kc, User manual – AERCO C-More Controls Manual June 2010 User Manual
Page 54

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
Page 54 of 162
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
04/22/14
GF-112
Phone: 800-526-0288
OMM-0032_0E
CALIBRATION POINTS
Valve Position % Open
Default Voltage Settings
UNIT TYPE & SIZE
FUEL
18%
30%
40%
50%
70%
100%,
BMK LN CP 6000
Natural Gas
1.60v
3.00v
4.00v
5.00v
7.00v
10.00v
18%
30%
45%
65%
85%
100%
BMK LN CP 6000
Dual Fuel
Natural Gas
2.00v
2.00v
2.45v
3.70v
6.35v
8.50v
18%
30%
45%
65%
85%
100%
Propane
2.00v
2.00v
2.45v
3.70v
6.35v
8.50v
Table 3-2B: Combustion Cal Menu Default Settings (Version 3.08.xx)
CALIBRATION POINTS
Valve Position % Open
Default Voltage Settings
INN UNIT SIZE
FUEL
16%
20%
30%
40%
50%
60%
80%
100%
INN 600
Natural Gas
1.90v 2.05v 2.20v 2.50v 2.80v 3.00v 3.65v
4.40v
16%
20%
30%
40%
50%
60%
80%,
100%
INN 600
Propane
2.00v 2.50v 3.20v 3.50v 3.70v 3.80v 4.00v
4.10v
16%
20%
30%
40%
50%
60%
80%
100%
INN 800
Natural Gas
1.90v 2.00v 2.50v 3.10v 3.50v 3.85v 4.70v
5.45v
16%
20%
30%
40%
50%
60%
80%,
100%
INN 800
Propane
2.10v 3.00v 4.40v 4.50v 4.60v 4.70v 4.80v
5.00v
16%
20%
30%
40%
50%
60%
80%
100%
INN 1060
Natural Gas
1.90v 2.30v 2.80v 3.00v 3.60v 3.90v 4.80v
6.00v
16%
20%
30%
40%
50%
60%
80%,
100%
INN 1060
Propane
2.00v 2.70v 3.80v 4.00v 4.50v 4.90v 5.50v
6.25v
16%
20%
30%
40%
50%
60%
80%
100%
INN 1350
Natural Gas
1.90v 2.60v 4.20v 4.70v 5.00v 5.00v 5.50v
6.00v
16%
20%
30%
40%
50%
60%
80%,
100%
INN 1350
Propane
2.10v 2.30v 4.70v 5.00v 5.20v 5.40v 5.80v
6.25v