C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual
Page 53

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 53 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
CALIBRATION POINTS
Valve Position % Open
Default Voltage Settings
UNIT TYPE & SIZE
FUEL
18%
30%
40%
50%
70%
100%
BMK 2000
Natural Gas
1.40v
3.80v
4.30v
5.40v
6.40v
9.50v
16%
30%
40%
50%
70%
100%
Propane
2.10v
3.50v
3.90v
4.10v
4.10v
8.90v
16%
30%
40%
50%
70%
100%
BMK 2000
Dual Fuel
Natural Gas
2.10v
4.50v
4.50v
4.50v
4.80v
9.60v
16%
30%
40%
50%
70%
100%
Propane
2.10v
3.50v
3.90v
4.10v
4.10v
8.90v
16%
30%
40%
50%
70%
100%
BMK 2500
Natural Gas
2.20v
4.10v
4.80v
5.30v
6.80v
8.50v
18%
22%
30%
45%
70%
100%
Propane
2.00v
2.00v
3.30v
4.60v
5.60v
7.90v
16%
20%
30%
45%
70%
100%
BMK 2500
Dual Fuel
Natural Gas
2.15v
2.10v
3.95v
5.60v
6.60v
8.50v
18%
22%
30%
45%
70%
100%
Propane
2.00v
2.00v
3.30v
4.60v
5.60v
7.90v
14%
30%
40%
50%
70%
100%
BMK 3000
Natural Gas
2.80v
4.60v
5.00v
5.50v
6.90v
9.10v
18%
30%
45%
65%
85%
100%
Propane
2.30v
4.40v
5.60v
5.70v
7.00v
8.60v
14%
30%
45%
65%
85%
100%
BMK 3000
Dual Fuel
Natural Gas
2.40v
5.40v
6.60v
7.00v
8.00v
8.70v
18%
30%
45%
65%
85%
100%
Propane
2.30v
4.40v
5.60v
5.70v
7.00v
8.60v
18%
30%
45%
60%
75%
100%
BMK LN CP 3.0
Propane
1.50v
4.00v
4.50v
4.30v
7.60v
10.00v
14%
30%
40%
50%
70%
100%
Natural Gas
1.60v
3.00v
4.00v
5.00v
7.00v
10.00v
18%
30%
45%
65%
85%
100%
BMK LN CP 3.0
Dual Fuel
Natural Gas
1.60v
3.00v
4.00v
5.00v
7.00v
10.00v
18%
30%
45%
60%
75%
100%
Propane
1.50v
4.00v
4.50v
4.30v
7.60v
10.00v