C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual
Page 15

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 15 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
Table 1-2: Operating Controls, Indicators and Displays - Continued
ITEM
NO.
CONTROL, INDICATOR
OR DISPLAY
FUNCTION
10
MENU KEYPAD
Consists of 6 keys which provide the following functions for the Control Panel Menus:
MENU
Steps through the main menu categories shown in Figure 2-1.
The Menu categories wrap around in the order shown.
BACK
Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key will
bring you back to the default status display in the VFD. Also,
this key allows you to go back to the top of a main menu
category.
▲ (Up) Arrow
When in one of the main menu categories (Figure 1-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the
▲ arrow key will increment the selected setting.
▼ (Down) Arrow
When in one of the main menu categories (Figure 1-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the
▼ (Down) arrow key will increment the selected
setting.
CHANGE
Permits a setting to be changed (edited). A valid password
must be entered before changing most menu items. When
the CHANGE key is pressed, the displayed menu item will
begin to flash. Pressing the
▲ or ▼ arrow key when the item
is flashing will increment or decrement the displayed setting.
ENTER
Saves the modified menu information in memory. The
display will stop flashing.
11
AUTO/MAN Switch
This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the MANUAL
status LED lights.
When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.
12
VALVE POSITION
Bargraph
20 segment red LED bargraph continuously shows the Valve
Open Position in 5% increments from 0 to 100%