beautypg.com

C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual

Page 15

background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 15 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Table 1-2: Operating Controls, Indicators and Displays - Continued

ITEM

NO.

CONTROL, INDICATOR

OR DISPLAY

FUNCTION

10

MENU KEYPAD

Consists of 6 keys which provide the following functions for the Control Panel Menus:

MENU

Steps through the main menu categories shown in Figure 2-1.
The Menu categories wrap around in the order shown.

BACK

Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key will
bring you back to the default status display in the VFD. Also,
this key allows you to go back to the top of a main menu
category.

▲ (Up) Arrow

When in one of the main menu categories (Figure 1-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the

▲ arrow key will increment the selected setting.

▼ (Down) Arrow

When in one of the main menu categories (Figure 1-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is flashing,
pressing the

▼ (Down) arrow key will increment the selected

setting.

CHANGE

Permits a setting to be changed (edited). A valid password
must be entered before changing most menu items. When
the CHANGE key is pressed, the displayed menu item will
begin to flash. Pressing the

▲ or ▼ arrow key when the item

is flashing will increment or decrement the displayed setting.

ENTER

Saves the modified menu information in memory. The
display will stop flashing.

11

AUTO/MAN Switch

This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the MANUAL
status LED lights.

When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.

12

VALVE POSITION
Bargraph

20 segment red LED bargraph continuously shows the Valve
Open Position in 5% increments from 0 to 100%