C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 27 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Table 2-5: Tuning Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Prop Band

1°F

120°F

70°F (Boiler)

8°F (Water Heater)

Integral Gain

0.00

2.00

1.00 (Boiler)

1.60 (Water Heater)

Derivative Time

(If Unit Type = Boiler)

0.00 min

2.00 min

0.00 min (Boiler)

0.10 min (Water Heater)

Min Load Adj

(If Unit Type = Water Heater)

-50°F

50°F

0°F

Max Load Adj

(If Unit Type = Water Heater)

-50°F

50°F

0°F

FFWD Temp

(If Unit Type = Water Heater)

30°F

245°F

Outlet Feedback

(If Unit Type = Water Heater)

On (Yes)

Off (No)

On (Yes)

Feedback Gain

(If Unit Type = Water Heater & Heatr
Tuning Dsp is Enabled)

.01

1.00

0.05

Breakpoints shown if Unit Type = Water Heater)

Breakpt at 100%*

30°F

240°F

77°F

Breakpt at 90%*

30°F

240°F

81°F

Breakpt at 80%*

30°F

240°F

85°F

Breakpt at 70%*

30°F

240°F

91°F

Breakpt at 60%*

30°F

240°F

95F

Breakpt at 50%*

30°F

240°F

102F

Breakpt at 40%*

30°F

240°F

110°F

Breakpt at 30%*

30°F

240°F

112°F

Breakpt at 20%*

30°F

240°F

114°F

Breakpt at 10%*

30°F

240°F

130°F

Breakpt at 0%*

30°F

240°F

135°F

Warmup Prop Band

Range 1-120

Default 95

Warmup Int Gain

Range 1-200

Default 50

Warmup PID Timer

Range 1-240

Default 20

Reset Defaults?

Yes, No, Are You Sure?

No