C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual
Page 27

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 27 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
Table 2-5: Tuning Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Prop Band
1°F
120°F
70°F (Boiler)
8°F (Water Heater)
Integral Gain
0.00
2.00
1.00 (Boiler)
1.60 (Water Heater)
Derivative Time
(If Unit Type = Boiler)
0.00 min
2.00 min
0.00 min (Boiler)
0.10 min (Water Heater)
Min Load Adj
(If Unit Type = Water Heater)
-50°F
50°F
0°F
Max Load Adj
(If Unit Type = Water Heater)
-50°F
50°F
0°F
FFWD Temp
(If Unit Type = Water Heater)
30°F
245°F
Outlet Feedback
(If Unit Type = Water Heater)
On (Yes)
Off (No)
On (Yes)
Feedback Gain
(If Unit Type = Water Heater & Heatr
Tuning Dsp is Enabled)
.01
1.00
0.05
Breakpoints shown if Unit Type = Water Heater)
Breakpt at 100%*
30°F
240°F
77°F
Breakpt at 90%*
30°F
240°F
81°F
Breakpt at 80%*
30°F
240°F
85°F
Breakpt at 70%*
30°F
240°F
91°F
Breakpt at 60%*
30°F
240°F
95F
Breakpt at 50%*
30°F
240°F
102F
Breakpt at 40%*
30°F
240°F
110°F
Breakpt at 30%*
30°F
240°F
112°F
Breakpt at 20%*
30°F
240°F
114°F
Breakpt at 10%*
30°F
240°F
130°F
Breakpt at 0%*
30°F
240°F
135°F
Warmup Prop Band
Range 1-120
Default 95
Warmup Int Gain
Range 1-200
Default 50
Warmup PID Timer
Range 1-240
Default 20
Reset Defaults?
Yes, No, Are You Sure?
No