background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 87 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

4. Into the textbox titled, Remote command type the full command line you wish to have

executed on the remote machine.

5. You are now ready to execute this command on the remote machine, simply click

the Open button at the bottom of the dialog.

6. You will have to provide an account name and password in the terminal window to

complete the process.

7.3 RS232 COMMUNICATION SETUP

Regardless of the terminal emulation utilized, the following guidelines must be adhered to when
setting up the RS232 communication link:

1. Baud Rate – The baud rates which can be used with the C-More Control Panel are:

(a)

2400

(b)

4800

(c)

9600 (Default)

(d)

19.2K

2. Data Format – The program must be set for: 8 data bits, 1 stop bit, no parity and either

Xon/Xoff or No flow control.

7.4 MENU PROCESSING UTILIZING RS232 COMMUNICATION

Viewing data logs and viewing or changing Control Panel menu options using RS232
communication is accomplished as follows:

1. Start the emulator software program and ensure that the specified baud rate and data

formats have been entered.

2. Press the Enter key on the laptop. An asterisk (*) prompt should appear.

3. At the prompt, enter the valid RS232 password (jaguar) in lower case letters and press

Enter.

4. “Welcome to Aerco” will appear in the laptop or “dumb terminal” display with a listing of

the following available entry choices:

M = Display next Menu
D = Display menu items
N = Display next menu items
Cxx = Change item xx
F = Fault log display
S = Sensor log display
T = Time line display
L = Log off

NOTE

The Level 1 password must be entered to change options in the
Setup, Configuration and Tuning Menus. The Level 2 password
must be entered to view or change options in the Calibration and
Diagnostics Menus.

With the exception of the password entry, all other keyboard
entries can be made using either upper or lower case.