C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 134 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

Option 7 – Continued



Step 3: Configure ALL C-More Units

On ALL Boilers:

1. Go to the Configuration Menu and set the BST Menu item to Enabled.

2. Go to the BST Menu and set the BST Mode item to BST Slave (for now).

On MASTER only:

3. Go to the BST Setpoint item and enter the Failsafe Setpoint.

4. Go to the BST Setup Menu item and set to Enabled.

5. Go to the BST Setpoint Mode item and select Remote Setpoint.

6. Go to the BST Remote Signal and select either 4-20ma or 0-20ma.

7. Go to the Head Temp Source item and select Network.

8. Go to the Header Temp Addr item and enter the Modbus Address (240).

9. Go to the Header Temp Point item and enter the Modbus Point (14).

When ALL C-More units have been configured:

10. Go to the BST Menu of the desired Master unit and set the BST Mode item to BST

MASTER.