2 keypad test, 3 relay test, Keypad test – AERCO C-More Controls Manual June 2010 User Manual

Page 81: Relay test, C-more controller for benchmark, innovation & kc

background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 81 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

3.

Press the ▲ key. LEDs will be displayed and the seven panel LEDs will light. These
LEDs are: COMM, MANUAL, REMOTE, DEMAND, °F, °C and FAULT.

4.

Press the ▲ key. 7-SEG will be displayed and all segments of the three-digit 7-
segment display will light.

5.

Press the ▲ key. Bar-graph will be displayed and the 20 segment VALVE POSITION
bargraph will light.

6. This completes the Display Test. Press the BACK key to exit the test.

6.3.2

Keypad Test

The Keypad Test checks the status of the eight keypad keys on the front panel. The test is
initiated as follows:

1. Press the

▲ or ▼ arrow key until Keypad Test Off is displayed.

2. Press the CHANGE key. Keypad Test will begin to flash.

3. Press each of the keys in the following sequence and verify that the name of each key

appears in the panel display:

(a)

AUTO/MAN (Manual is displayed).

(b)

MENU

(c)

▲ (Up is displayed)

(d)

▼ (Down is displayed)

(e)

CHANGE

(f)

ENTER

(g)

CLEAR

4. Press the BACK key to exit the Keypad Test.

6.3.3

Relay Test

The Relay Test allows the user to switch relays ON or OFF. The relays which are tested are:
Igniter, Blower, Pump, Aux and Fault relays. The Aux and Fault relays are located in the I/O
Box on the left side of the unit. Removing the cover on the I/O Box will permit the ON/OFF
status of these relays to be observed. The remaining relays are located in the C-More Control
Panel. A “click” can be heard as each relay is turned ON and OFF.

1. Press the

▲ or ▼ arrow key until Relay Test Off is displayed.

2. Press the CHANGE key. Relay Test will begin to flash.

3.

Press the ▲ arrow key. Fault OFF will be displayed.

4. To switch relay to ON, press ENTER. Fault ON will be displayed. Press ENTER again

to toggle relay back to OFF. The ON/OFF status of this relay can be observed with the
I/O Box cover removed.

5. To change the ON/OFF status of the remaining relays, repeat steps 3 and 4. The

display will show the relays in the following order:

(a)

Aux

(b)

Pump

(c)

Blower