11 diagnostics menu, Diagnostics menu, C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual
Page 30

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
Page 30 of 162
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
04/22/14
GF-112
Phone: 800-526-0288
OMM-0032_0E
Table 2-8: Calibration Menu - Continued
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Heatr Bkpt Dsp
(If Unit Type = Water Heater)
Enabled or Disabled
Disabled
Stop Level
0%
Start Level
16
Start Level
Stop Level
40%
20
Skip Range Cntr
10
95
40
Skip Range Span
0
3
0
Skip Speed
5
20
5
O2 Gain
920
1126
1024
O2 Offset
-3.0
+3.0
0
FFWD Temp Offset
-20
+20
0
Exhst Tmp Offset
-20
+20
0
Outdr Air Offset
-20
+20
0
Inlet Air Offset
-20
+20
0
Inlet Wtr Offset
-20
+20
0
Outlet Wtr Offset
-20
+20
0
0 – 10v Out Test
0.00
10.00
2.11 DIAGNOSTICS MENU
The Diagnostics Menu shown in Table 2-9 is used by Factory-Trained Service personnel to
troubleshoot the unit. This menu category contains a number of Built In Test (BIT) test routines
to be used to check the operational status of the Control Panel displays and keypad keys. It
also allows the operator to activate relays, view switch status and increment the stepper motor
contained in the Air/Fuel Valve.
NOTE
With the exception of the Sensor Log Interval (Int) setting, none of
the following Diagnostic Menu items can be initiated via a remote
serial communications link.