Table 2-3: Configuration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

KC Boiler, KC Boiler LN, BMK Boiler Std,

BMK Boiler LN, BMK Blr Std Dual, BMK

Blr LN KC Water Heater,

KC Wtr Heater LN, Innovation WH

BMK Boiler LN

Unit Size

600 MBH, 750 MBH, 800 MBH 1000 MBH,

1060 MBH, 1500 MBH, 2000 MBH, 3000

MBH

1000 MBH

Fuel Type

Natural Gas, Propane

Natural Gas

Boiler Mode

Constant Setpoint, Remote Setpoint,

Direct Drive, Combination, Outdoor Reset

Constant

Setpoint

Remote Signal
(If Mode = Remote Setpoint, Direct
Drive or Combination)

4 – 20 mA/1 – 5V, 0 -20 mA/0 – 5V

PWM Input (BMS), Network

4 – 20 mA, 1-5V

Bldg Ref Temp, (If Mode = Outdoor
Reset)

40°F

230°F

70°F

Reset Ratio, (If Mode = Outdoor Reset)

0.1

9.9

1.2

Outdoor Sensor

Enabled or Disabled

Disabled

System Start Tmp. (If Outdoor Sensor =
Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

220°F

200°F

Temp Hi Limit

40°F

240°F

210°F

Max Valve Position

40%

100%

100%

Pump Delay Timer

0 min.

30 min.

0 min.

Aux Start On Dly

0 sec.

120 sec.

0 sec.

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

*Analog Output
(See CAUTION at end of Table)

Off, Setpoint, Outlet Temp,

Valve Position 4-20 mA,

Valve Position 0-10V

*Valve Position

0-10V

Low Fire Timer

2 sec.

600 sec.

2 sec.

Setback Limiting

Enabled or Disabled

Disabled