Table 2-3: Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
KC Boiler, KC Boiler LN, BMK Boiler Std,
BMK Boiler LN, BMK Blr Std Dual, BMK
Blr LN KC Water Heater,
KC Wtr Heater LN, Innovation WH
BMK Boiler LN
Unit Size
600 MBH, 750 MBH, 800 MBH 1000 MBH,
1060 MBH, 1500 MBH, 2000 MBH, 3000
MBH
1000 MBH
Fuel Type
Natural Gas, Propane
Natural Gas
Boiler Mode
Constant Setpoint, Remote Setpoint,
Direct Drive, Combination, Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct
Drive or Combination)
4 – 20 mA/1 – 5V, 0 -20 mA/0 – 5V
PWM Input (BMS), Network
4 – 20 mA, 1-5V
Bldg Ref Temp, (If Mode = Outdoor
Reset)
40°F
230°F
70°F
Reset Ratio, (If Mode = Outdoor Reset)
0.1
9.9
1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp. (If Outdoor Sensor =
Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
220°F
200°F
Temp Hi Limit
40°F
240°F
210°F
Max Valve Position
40%
100%
100%
Pump Delay Timer
0 min.
30 min.
0 min.
Aux Start On Dly
0 sec.
120 sec.
0 sec.
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
*Analog Output
(See CAUTION at end of Table)
Off, Setpoint, Outlet Temp,
Valve Position 4-20 mA,
Valve Position 0-10V
*Valve Position
0-10V
Low Fire Timer
2 sec.
600 sec.
2 sec.
Setback Limiting
Enabled or Disabled
Disabled